Plan Review Notes
Plan Review Notes For Permit 09010335
Permit Number 09010335
Review Stop E
Sequence Number 3
Notes
Date Text
2009-07-31 18:06:45 
 ** DENIED 3RD REVIEW **
  
 *** NOTES SPECIFIC TO THE TWO PREVIOUS REVIEWS ARE
 STILL NOT ADDRESSED MEETING MINIMUM FLORIDA BUILDING
 CODE REQUIREMENTS. IT SHOULD BE NOTED THAT FS
 553.80(2)(B) IS NOT ASSESSED ONLY DUE TO THE FACT THE
 SAME DESIGN PROFESSIONAL HAS NOT BEEN RESPONSIBLE FOR
 THE ENERGY CALCULATIONS EACH TIME THE PLANS HAVE BEEN
 SUBMITTED. THE FACT IS THE NEW SUBMITTED ENERGY
 CALCULATIONS ARE NOW SIGNED, DATED AND SEALED BY A NEW
 DESIGNER THAN SUBMITTED ON THE PREVIOUS CALCULATIONS.
 PLEASE SEE THE STATUTE NOTED ABOVE AS IT STATES THE
 *SAME SPECIFIC CODE SECTION NOTED*. THE SAME CODE
 SECTION HAS BEEN REPEATED THREE TIMES.
 THE 4X FEE IS NOT ASSESSED AT THIS TIME.
  
  
 1) NOTE: PLEASE SEE FBC 13-415.2.ABC.1.1,.1.2 AND .1.3.
 ALL LIGHTING ON PLANS SHALL BE PLACED INTO THE INPUT
 DATA REPORT OF THE SUBMITTED ENERGY CALCULATIONS
 SHOWING MINIMUM CODE COMPLIANCE. IT WAS SPECIFICALLY
 NOTED BY THIS REVIEW THAT ALL NEW PARKING LOT LIGHTING
 FIXTURES HAD BEEN ADDED YET NONE OF THESE WERE PLACED
 INTO THE SUBMITTED ENERGY CALCULATIONS.
 PLEASE SEE THE IDR WHICH DOES NOT INDICATE *ANY* OF THE
 PARKING LOT FIXTURES. THIS IS POSSIBLE WHEN PARKING LOT
 LIGHTING FIXTURES ARE COVERED BY THE SECTIONS NOTED
 ABOVE. PLEASE BE SURE TO SEE 13-415.2.ABC.1.3, AND
 PLEASE BE SURE TO SEE THE 2006 REVISIONS TO THE 2004
 FBC AS THE PROJECT IS UNDER THE 2004 FBC.
 THE IDR ONLY INDICATES TWO OF THE THREE 52 WATT
 FIXTURES SHOWN ON PLANS. IF THIS WAS THE ONLY FIXTURE
 MISSING THIS WOULD NOT BE CONSIDERED TO FAIL
 CALCULATIONS. PLEASE SEE13-103.3 AS IT STATES THE
 FOLLOWING:
 *BUILDING OFFICIALS OR THEIR OFFICIALLY DESIGNATED
 REPRESENTATIVES SHALL ASSURE THAT THE COMPLIANCE FORMS
 ARE COMPLETE AND WITHOUT GROSS ERRORS.*
  
 ** IT IS NOTED FOR INFORMATION ONLY TO SEE OTHER
 POSSIBLE ITEMS ON THE IDR WHICH ARE NOT THE SAME AS
 PRODUCTS ON PLANS. FOR EXAMPLE: IDR STATES *CARPET AND
 RUBBER PADDING* FOR ALL AREAS. SEE BUILDING REVIEW OR
 PLUMBING REVIEW COMMENTS FOR AREAS SUCH AS BATHROOMS
 WHICH ARE NOT PERMITTED TO BE CARPET AND RUBBER PADDED.
 THIS IS NOTED ONLY AS A CREDIT IS BEING TAKEN.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  