2009-08-06 19:19:17BUILDING REVIEW APPROVED WITH PROVISO (PROVIDE
 INFORMATION PRIOR TO INSPECTION TO AVOID CONFLICTS OR
 DELAYS):
  
 1- DRESSING ROOM TO COMPLY WITH SEC. 11-4.35.1 THRU
 11-4.35.4. PROVIDE REVISED PLAN AND DETAIL SHOWING
 COMPLIANCE WITH THIS SECTIONS.
  
 2- PROVIDE COMPLETE TRUSS PACKAGE REVIEWED BY THE
 DESIGNER OF RECORD PRIOR TO INSTALLATION.
  
 3- PROVIDE COMPLETE ENGINEERING AND SPECIFICATIONS FOR
 LIGHT POLES SHOWN ON SHEET SEP-1.
  
 4- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING IN FLAT ROOF ASSEMBLY AS REQUIRED BY
 GENERAL LIMITATION #7 ON NOA SUBMITTED. CLEARLY
 IDENTIFY SELECTED ASSEMBLY AND BASE SHEET FASTENING
 OPTION.
  
 5- ENGINEER WHO SEALED ASBESTOS REPORT NEEDS TO USE
 CURRENT SEAL THAT SAYS "LICENSE" NOT "CERTIFICATE" AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 6- PROVIDE COMPLETE PRODUCT APPROVAL FOR ROLL DOWN
 SHUTTERS. PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE
 THAT CORRESPONDS TO INFORMATION SUBMITTED.
  
 7- REVISE ACCORDION SHUTTERS INSTALLATION SCHEDULE.
 REVISE SHUTTERS MOUNTING CONDITION, SHUTTERS
 INSTALLATION (VERTICAL NOT HORIZONTAL) AND ANCHOR
 SPACING. SEE PRODUCT APPROVAL SUBMITTED.
  
 8- PROVIDE PRODUCT APPROVAL FOR EXTERIOR INSWING DOOR
 (RULE 9B-72) AS SHOWN ON PLANS.