2009-04-14 19:10:01 | ** DENIED/** |
| |
| |
| |
| 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS DO NOT |
| COMPLY WITH THE FOLLOWING. THE FBC 13-103.1, FS |
| 471.025, FAC 61G15-23.002 |
| BOTH COPIES IN SETS OF DOCUMENTS SUBMITTED DO NOT MEET |
| MINIMUM SECTIONS ABOVE. ONE COPY SUBMITTED IS IN FACT A |
| COLORED PHOTO-COPY OF SIGNED DOCUMENTS. IN EITHER CASE |
| BOTH SUBMITTED ARE NOT SEALED AS REQUIRED. |
| THE CALCULATIONS CERTIFICATION SHEET CONTAINS THE |
| STRUCTURAL ENGINEER AS THE PERSON WHOM THE CALCULATIONS |
| ARE PREPARED BY ALONG WITH A PRINTED NAME AND SIGNATURE |
| YET NO RAISED SEAL IS PRESENT. PLEASE CONFIRM THE |
| CALCULATIONS ARE DONE BY MR. GORDON BUCK. THE |
| CALCULATIONS ALSO CONTAIN THE PRINTED NAME AND |
| SIGNATURE FROM MR. MARIO FERNANDEZ WHO IS SHOWN AS THE |
| MECHANICAL AND ELECTRICAL ENGINEER. |
| |
| 2) NOTE: LIGHTING ON THE INPUT DATA REPORT STILL NEEDS |
| TO COORDINATE WITH THE SUBMITTED PLANS. PLEASE TAKE A |
| LOOK AT EXTERIOR FIXTURES ON PLANS. BY THE SYMBOL |
| LEGEND ALL OF THESE ARE SHOWN AS RECESSED FLUORESCENT |
| DOWN LIGHTS. HOW IS THIS POSSIBLE ON THE EXTERIOR |
| WALLS? |
| PLEASE SEE THE IDR AS NONE OF THE SITE PARKING LOT |
| LIGHTS WHICH ARE NOW ON PLANS FOR THE FIRST TIME ARE |
| INCLUDED. HOW IS THIS POSSIBLE? |
| PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND SECTION .1.3 FOR |
| EXTERIOR LIGHTING. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |