Plan Review Notes
Plan Review Notes For Permit 09010335
Permit Number 09010335
Review Stop P
Sequence Number 1
Notes
Date Text
2009-03-02 16:45:32DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH BUCK ENGINEERING INC. THE ENGINEERS
 LICENSE NUMBER IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET. FAC 61G15-23.002(2) & FS 471.025.
  
 2. SHT 1.1 EXISTING PLAN VIEW. THE APPLICATION FOR
 PERMIT DESCRIPTION OF PROJECT STATES, "RELOCATING
 EXISTING OLD BATHROOMS". EXISTING BATHROOMS ARE NOT
 SHOWN ON THE EXISTING PLAN VIEW. PLEASE INDICATE THE
 LOCATION OF THE EXISTING BATHROOMS. SECTIONS 106.1.2,
 106.1.3, 106.1.1, 701.1 & 704.5.
  
 3. SHT 2.1 CODES FOR THIS PROJECT SHALL INCLUDE THE
 2007 REVISIONS TO THE FLORIDA BUILDING CODE. SECTION
 106.1.1.
  
 4. SHT 5.1 PER SECTION 1107.2 SEPARATE SECONDARY ROOF
 DRAINS ARE REQUIRED AND PER SECTION 1503.4.3 OF THE
 BUILDING CODE THE OVERFLOW SCUPPER SHALL BE A MINIMUM
 OF 2" AND A MAXIMUM OF 4" OFF THE ROOF TO THE FLOW
 LINE. PLEASE SUBMIT A DETAIL/ELEVATION SHOWING THE
 SEPARATE OVERFLOW SCUPPERS AND COMPLIANCE WITH
 1503.4.3.
  
 5. SHTS 2.1 & 6.1 THE CLEAR FLOOR SPACE FOR THE
 DRINKING FOUNTAIN IS REQUIRED TO BE FORWARD APPROACH.
 SECTION 11-4.15.5. SHT 2.1 SHOWS PARALLEL APPROACH.
 PLEASE CHANGE THE CLEAR FLOOR SPACE TO REFLECT THE
 REQUIRED APPROACH.
  
 6. SHT 8.1 THE SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN. THE FLOOR DRAIN BY THE SERVICE SINK AND
 THE FLOOR DRAIN BY THE WATER HEATER AS WELL AS THE 3"
 STUB UP FOR FUTUREUSE ARE NOT SHOWN ON THE RISER.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 701.1.
  
 7. SHT 8.1 PLUMBING PLAN SHOWS NO SANITARY PIPING TO
 THE SERVICE SINK, NO VENT FOR THE FLOOR DRAIN BY THE
 WATER HEATER, NO VENT FOR THE FUTURE STUB UP IN PHASE
 II, NOR DOES IT SHOW THE BUILDING DRAIN EXITING THE
 BUILDING AND CONNECTING TO THE BUILDING SEWER AS WELL
 AS THE CLEANOUTS REQUIRED BY SECTIONS 708.3.1 &
 708.3.5. SECTIONS 106.1.1, 701.1, 901.1.
  
 8. SHT 8.1 THERMAL EXPANSION CONTROL IS REQUIRED PER
 SECTION 607.3.2. PLEASE INDICATE METHOD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved