Date |
Text |
2009-03-02 16:45:32 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. ALL SHEETS WITH BUCK ENGINEERING INC. THE ENGINEERS |
| LICENSE NUMBER IS REQUIRED IN THE TITLE BLOCK OF EACH |
| SHEET. FAC 61G15-23.002(2) & FS 471.025. |
| |
| 2. SHT 1.1 EXISTING PLAN VIEW. THE APPLICATION FOR |
| PERMIT DESCRIPTION OF PROJECT STATES, "RELOCATING |
| EXISTING OLD BATHROOMS". EXISTING BATHROOMS ARE NOT |
| SHOWN ON THE EXISTING PLAN VIEW. PLEASE INDICATE THE |
| LOCATION OF THE EXISTING BATHROOMS. SECTIONS 106.1.2, |
| 106.1.3, 106.1.1, 701.1 & 704.5. |
| |
| 3. SHT 2.1 CODES FOR THIS PROJECT SHALL INCLUDE THE |
| 2007 REVISIONS TO THE FLORIDA BUILDING CODE. SECTION |
| 106.1.1. |
| |
| 4. SHT 5.1 PER SECTION 1107.2 SEPARATE SECONDARY ROOF |
| DRAINS ARE REQUIRED AND PER SECTION 1503.4.3 OF THE |
| BUILDING CODE THE OVERFLOW SCUPPER SHALL BE A MINIMUM |
| OF 2" AND A MAXIMUM OF 4" OFF THE ROOF TO THE FLOW |
| LINE. PLEASE SUBMIT A DETAIL/ELEVATION SHOWING THE |
| SEPARATE OVERFLOW SCUPPERS AND COMPLIANCE WITH |
| 1503.4.3. |
| |
| 5. SHTS 2.1 & 6.1 THE CLEAR FLOOR SPACE FOR THE |
| DRINKING FOUNTAIN IS REQUIRED TO BE FORWARD APPROACH. |
| SECTION 11-4.15.5. SHT 2.1 SHOWS PARALLEL APPROACH. |
| PLEASE CHANGE THE CLEAR FLOOR SPACE TO REFLECT THE |
| REQUIRED APPROACH. |
| |
| 6. SHT 8.1 THE SANITARY RISER DIAGRAM DOES NOT REFLECT |
| THE FLOOR PLAN. THE FLOOR DRAIN BY THE SERVICE SINK AND |
| THE FLOOR DRAIN BY THE WATER HEATER AS WELL AS THE 3" |
| STUB UP FOR FUTUREUSE ARE NOT SHOWN ON THE RISER. |
| PLEASE CORRELATE. SECTIONS 106.1.1 & 701.1. |
| |
| 7. SHT 8.1 PLUMBING PLAN SHOWS NO SANITARY PIPING TO |
| THE SERVICE SINK, NO VENT FOR THE FLOOR DRAIN BY THE |
| WATER HEATER, NO VENT FOR THE FUTURE STUB UP IN PHASE |
| II, NOR DOES IT SHOW THE BUILDING DRAIN EXITING THE |
| BUILDING AND CONNECTING TO THE BUILDING SEWER AS WELL |
| AS THE CLEANOUTS REQUIRED BY SECTIONS 708.3.1 & |
| 708.3.5. SECTIONS 106.1.1, 701.1, 901.1. |
| |
| 8. SHT 8.1 THERMAL EXPANSION CONTROL IS REQUIRED PER |
| SECTION 607.3.2. PLEASE INDICATE METHOD. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |