Plan Review Notes
Plan Review Notes For Permit 09010335
Permit Number 09010335
Review Stop E
Sequence Number 1
Notes
Date Text
2009-02-18 16:12:22 
  
  
 *** DENIED ***
  
 1) NOTE: PLANS NEED TO CONTAIN ALL OF THE FOLLOWING
 RELEVANT CODES ON THE ELECTRICAL SHEETS.
 2004 FBC W/2007 REVISIONS
 2005 NFPA-70
 2006 NFPA-101
  
 FAC 69A-60.004, AND .003 WAS REVISED ON DECEMBER 31ST,
 2008 TO ADOPT THE NEW LIFE SAFETY CODE AND FLORIDA FIRE
 PREVENTION CODE.
  
 2) NOTE: THE SUBMITTED ENERGY CALCULATIONS DO NOT
 CONTAIN ANY SIGNATURE, DATE OR SEAL FOR PERSON
 RESPONSIBLE. THEY DO CONTAIN A PRINTED NAME OF A
 STRUCTURAL ENGINEER.
 PLEASE BE SURE TO SEE FS 471.025 FOR ENGINEER AS
 RESPONSIBLE DESIGNER.
 PLEASE ALSO SEE FBC 13-103.1 FOR CERTIFICATION OF
 COMPLIANCE REQUIRED.
 PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1, .1.2 AND
 .1.3 FOR ALL INFORMATION ON PLANS REGARDING LIGHTING
 WHICH IS REQUIRED TO COORDINATE WITH SPECIFIC LIGHTING
 ON PLANS.
 BASED ON THE SUBMITTED INPUT DATA REPORT WHICH
 ACCOMPANIES THE SUBMITTED ENERGY CALCULATIONS SUMMARY,
 THE IDR DOES NOT MATCH THE PLANS. THE PLANS ACTUALLY DO
 CONTAIN A GREATER NUMBER OF FIXTURES ALONG WITH HIGHER
 WATTAGES.
 PLEASE SEE THE INTERIOR LIGHTING ON THE IDR WHICH ONLY
 INDICATES 32W YET BASED ON THE FIXTURE LEGEND FIXTURE
 *A* FOR EXAMPLE ARE 2-32W BULBS.
 *B* FIXTURES ARE 3-32W.
 IN EITHER CASE THE VA RATING TO BE PART OF THE IDR IS
 BASED ON THE EFFICIENCY RATING OF THE FIXTURE/BALLAST
 VA.
 THIS IS VERY IMPORT AS POWER FACTORS ON BALLAST FOR
 EXAMPLE INCLUDING BUT NO LIMITED TO1.15 OR LOWER .86
 WHICH WILL GREATLY AFFECT CALCULATIONS. ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  