2009-02-18 16:12:22 | |
| |
| |
| *** DENIED *** |
| |
| 1) NOTE: PLANS NEED TO CONTAIN ALL OF THE FOLLOWING |
| RELEVANT CODES ON THE ELECTRICAL SHEETS. |
| 2004 FBC W/2007 REVISIONS |
| 2005 NFPA-70 |
| 2006 NFPA-101 |
| |
| FAC 69A-60.004, AND .003 WAS REVISED ON DECEMBER 31ST, |
| 2008 TO ADOPT THE NEW LIFE SAFETY CODE AND FLORIDA FIRE |
| PREVENTION CODE. |
| |
| 2) NOTE: THE SUBMITTED ENERGY CALCULATIONS DO NOT |
| CONTAIN ANY SIGNATURE, DATE OR SEAL FOR PERSON |
| RESPONSIBLE. THEY DO CONTAIN A PRINTED NAME OF A |
| STRUCTURAL ENGINEER. |
| PLEASE BE SURE TO SEE FS 471.025 FOR ENGINEER AS |
| RESPONSIBLE DESIGNER. |
| PLEASE ALSO SEE FBC 13-103.1 FOR CERTIFICATION OF |
| COMPLIANCE REQUIRED. |
| PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1, .1.2 AND |
| .1.3 FOR ALL INFORMATION ON PLANS REGARDING LIGHTING |
| WHICH IS REQUIRED TO COORDINATE WITH SPECIFIC LIGHTING |
| ON PLANS. |
| BASED ON THE SUBMITTED INPUT DATA REPORT WHICH |
| ACCOMPANIES THE SUBMITTED ENERGY CALCULATIONS SUMMARY, |
| THE IDR DOES NOT MATCH THE PLANS. THE PLANS ACTUALLY DO |
| CONTAIN A GREATER NUMBER OF FIXTURES ALONG WITH HIGHER |
| WATTAGES. |
| PLEASE SEE THE INTERIOR LIGHTING ON THE IDR WHICH ONLY |
| INDICATES 32W YET BASED ON THE FIXTURE LEGEND FIXTURE |
| *A* FOR EXAMPLE ARE 2-32W BULBS. |
| *B* FIXTURES ARE 3-32W. |
| IN EITHER CASE THE VA RATING TO BE PART OF THE IDR IS |
| BASED ON THE EFFICIENCY RATING OF THE FIXTURE/BALLAST |
| VA. |
| THIS IS VERY IMPORT AS POWER FACTORS ON BALLAST FOR |
| EXAMPLE INCLUDING BUT NO LIMITED TO1.15 OR LOWER .86 |
| WHICH WILL GREATLY AFFECT CALCULATIONS. ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |