2009-02-04 11:18:37 | BUILDING CHANGE OF USE/ALTERATION, BUILDING REVIEW |
| CHECKLIST. |
| REVIEW UNDER 2004 FBC WITH 2007 REVISIONS. |
| |
| 1- DESCRIPTION OF WORK SHOWN ON PERMIT APPLICATION |
| DOESN'T MATCH INFORMATION SHOWN ON PLANS SUBMITTED. |
| PLANS SHOW CHANGE OF USE FROM PARKING TO MERCANTILE. |
| REVISE DESCRIPTION ON PERMIT APPLICATION AS REQUIRED TO |
| MATCH PLANS. |
| |
| 2- BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT |
| FEES FOR CHANGE OF USE ARE REQUIRED. BRING BACK PALM |
| BEACH COUNTY STAMPED PLANS AND COPY OF THE PAID RECEIPT |
| IF FEES ARE DUE. IF THIS WAS DONE BEFORE, PLEASE GET |
| THE PLANS RE-STAMPED AND BRING COPY OF PAID RECEIPT. WE |
| NEED THIS INFORMATION FOR RECORD KEEPING. |
| |
| 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| |
| 4- ACCORDING TO PROPERTY APPRAISAL WEBSITE AERIAL VIEW |
| OF THE BUILDING (SEE ATTACHED COPY) AND DEFINITION FOR |
| BUILDING AREA ON CHAPTER SEC. 502 OF 2004 FBC THE |
| BUILDING IS TO BE CONSIDERED AS ONE BUILDING. NEED TO |
| PROVIDE COMPLETE INFORMATION FOR ENTIRE BUILDING TO |
| VERIFY COMPLIANCE WITH: |
| A) TOTAL BUILDING AREA ALLOWED ACCORDING TO THE |
| BUILDING CONSTRUCTION TYPE. PROVIDE CALCULATIONS TO |
| VERIFY COMPLIANCE WITH TABLE 503 FBC 2004. |
| |
| B) PERCENTAGE OF OPENINGS ALLOWED, INCLUDING PROTECTED |
| AND UNPROTECTED OPENINGS AS REQUIRED BY TABLE 704.8 FBC |
| 2004. |
| |
| C) SEPARATION BETWEEN OCCUPANCIES. TABLE 302.3.2 FBC |
| 2004. |
| NOTE: TAKE INTO CONSIDERATION FIRE RATING OF DOORS AND |
| WINDOWS ON WALKWAY BETWEEN THRIFT SHOP AND STORAGE. |
| TABLE 704.8 FBC 2004. |
| |
| 5- ENGINEER NEEDS TO WRITE DOWN HIS LICENSE NUMBER AS |
| REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE |
| CODE. PLANS ONLY SHOW THE ENGINEERING FIRM CERTIFICATE |
| OF AUTHORIZATION NUMBER, NOT THE ENGINEER'S LICENSE |
| NUMBER. THIS APPLIES TO TITLE BLOCK ON ALL SHEETS. |
| |
| 6- SHEET 2.1: |
| A) GENERAL NOTES ON THE BOTTOM LEFT OF SHEET DON'T |
| CORRESPOND TO THIS PROJECT. THEY CORRESPOND TO AN |
| EATING PLACE LIKE SUBWAY. REVISE NOTES AS REQUIRED TO |
| INCLUDE ONLY THE ONES THAT PERTAIN TO THIS JOB. |
| |
| B) UPDATE CODES FOR THIS PROJECT. REFER TO FBC 2004 |
| WITH 2007 REVISIONS, NOT 2006. ALSO, THE SCOPE OF WORK |
| INCLUDES CHANGE OF OCCUPANCY. SEE CHAPTER 8 OF 2004 |
| FLORIDA EXISTING BUILDING CODE. |
| |
| C) PROJECT DATA AT THIS TENANT INFORMATION: COORDINATE |
| ALL INFORMATION WITH ITEM #4 ABOVE. |
| IN ADDITION CLARIFY THE FOLLOWING: |
| * WHERE WAS GROUP M "ORDINARY HAZARD" TERM AND STORAGE |
| S-1 "ORDINARY HAZARD" TERM TAKEN FROM. WHAT DOES |
| "ORDINARY HAZARD" MEANS. SPECIFY CODE SECTION OR TABLE |
| WHERE THIS WAS TAKEN FROM. |
| |
| ** GENERAL HEIGHT AND AREA INFORMATION IS INCORRECT |
| BASED ON THE TYPE OF CONSNTRUCTION IIIB. REVISE AS |
| REQUIRED. |
| |
| *** REVISE FIRE RATED CORRIDORS INFORMATION. SEE TABLE |
| 1016.1 FBC 2004. |
| |
| **** REVISE MAXIMUM TRAVEL DISTANCE. ACCORDING TO |
| CONSTRUCTION TYPE SHOWN THIS IS TYPE III UNSPRINKLERED. |
| |
| ***** REVISE INFORMATION GIVEN ON CONSTRUCTION |
| CLASIFICATION PER TABLE 602 FBC 2004. INFORMATION IS |
| NOT CLEAR, FIRE RATING IS NOT SPECIFIED AND NEED TO |
| COORDINATE THIS INFORMATION WITH ITEM #4 ABOVE. |
| |
| ****** CLARIFY WHERE IS THE NUMBER OF PEOPLE CONSIDERED |
| FOR THE STORAGE AREA TAKEN FROM. THIS NUMBER DOESN'T |
| WORK WITH TABLE 1004.1.2 FBC 2004. IT CAN'T HAVE MORE |
| PEOPLE THAN THAT ALLOWED BY THE TABLE. |
| |
| D) REVISE DESIGN PARAMETERS INFORMATION: WHERE IS |
| SECTION 1609.6A-D TAKEN FROM. SEE CODE FOR CORRECT CODE |
| SECTIONS TO BE REFERENCED. |
| |
| E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR RAMP |
| HANDRAILS IN CORRIDOR BETWEEN THRIFT STORE AND STORAGE |
| TO VERIFY COMPLIANCE WITH SEC. 11-4.8.5 FBC 2004. |
| |
| F) PROVIDE COMPLETE INFORMATION TO VERIFY IF HANDRAILS |
| ARE REQUIRED OR NOT ON RAMP GOING TO THE THRIFT STORE |
| BY EAST WALL SINGLE DOOR. |
| |
| G) LANDING ON EAST RAMP BY SINGLE ENTRY DOOR DOESN'T |
| COMPLY WITH SEC. 11-4.8.4 FBC 2004. REVISE AS REQUIRED. |
| |
| H) MANEUVERING CLEARANCES AT DOOR LEADING TO THE WOMEN |
| TOILET ROOM DOESN'T COMPLY WITH FIGURE 25 OF CHAPTER 11 |
| FBC 2004. PROVIDE DIMENSIONS SHOWING COMPLIANCE. |
| |
| I) INFORMATION ON INTERIOR WALL DETAIL AND GENERAL WALL |
| LEGEND DOESN'T MATCH. REVISE STUD SPACING TO MATCH. |
| |
| J) PROVIDE COMPLETE CALCULATIONS SHOWING HOW THE |
| DIMENSIONS FOR ALLOWED WALL OPENINGS WHERE TAKEN FROM. |
| IN ADDITION. NEED TO COORDINATE THIS INFORMATION WITH |
| ITEM #4 ABOVE. PROVIDE SKETCH SHOWING CONSIDERED WALL |
| AREAS AND CORRESPONDING DISTANCES. |
| |
| K) SHOW OVERALL BUILDING FOOTPRINT. COORDINATE WITH |
| ITEM #4 ABOVE. |
| |
| 7- SHEET 5.1: |
| A) PARAPET WALL DETAIL: PARAPET WALL TO HAVE THE SAME |
| FIRE-RESISTANCE RATING AS THE WALL SUPPORTING IT AS |
| REQUIRED BY SEC. 704.11.1 FBC 2004. REVISE AS REQUIRED. |
| |
| B) SHEET 2.1 SPECIFIES TYPE IIIB CONSTRUCTION TYPE. |
| REVISE PARAPET CONSTRUCTION AS REQUIRED TO MATCH TYPE |
| OF CONSTRUCTION SPECIFIED FOR THE BUILDING. |
| |
| C) PROVIDE COMPLETE TRUSS ENGINEERING PACKAGE. TRUSS |
| PACKAGE NEED TO BE REVIEWED AND APPROVED IN WRITING BY |
| THE ENGINEER OF RECORD PRIOR TO SUBMITTAL TO THIS |
| OFFICE. |
| |
| D) COMPONENTS AND CLADDING PRESSURES ZONES FOR ROOF |
| SCHEDULE: CLARIFY WHY SPACING FOR NAILS AT INTERMEDIATE |
| SUPPORTS IS NOT GIVEN FOR ROOF ZONE #3. |
| |
| E) PLYWOOD ROOF SHEATHING SPECIFICATIONS SHOWN ON |
| PARAPET WALL DETAIL DON'T MATCH SPECIFICATIONS SHOWN ON |
| COMPONENTS AND CLADDING SCHEDULE AND ON PLYWOOD |
| SHEATHING NAILING SCHEDULE NOTE AT BOTTOM RIGHT CORNER |
| OF SHEET. REVISE AS REQUIRED. |
| |
| F) ROOF DESIGN LOADS TO MATCH LOADS SPECIFIED ON SHEET |
| 2.1. |
| |
| G) ROOF FRAMING PLAN: CLARIFY WHY NEW GUTTER BY OTHERS |
| ON EXISTING HIGHER ROOF. THERE IS NOT BUILDING SECTION |
| ON SHEET 7 AS SPECIFIED ON NOTE. PROVIDE ALL PERTINENT |
| INFORMATION AS REQUIRED. CLARIFY IF A SEPARATE PERMIT |
| WILL BE APPLIED FOR THE GUTTER. |
| |
| 8- SHEET 6.1: |
| A) COMPONENTS AND CLADDING PRESSURES ZONES FOR WALLS |
| SCHEDULE: CLARIFY WHY THE NAIL SPACING IS MORE CLOSER |
| TOGETHER FOR ZONE 4 THAN FOR ZONE 5. |
| |
| B) CLARIFY WHY THERE IS NOT NAILING SPECIFICATIONS FOR |
| INTERMEDIATE SUPPORTS ON ZONE 4 OF COMPONENTS AND |
| CLADDING SCHEDULE. |
| |
| C) STRUCTURAL DOOR BUCK DETAIL: SEE SUBMITTED PRODUCT |
| APPROVAL AND REVISE DOOR BUCK DETAIL AS REQUIRED. |
| |
| D) SOME SIZE OF WINDOWS SHOWN ON ELEVATIONS DON'T MATCH |
| SIZE OF WINDOWS SPECIFIED ON FLOOR PLAN ON SHEET 2.1. |
| REVISE AS REQUIRED TO MATCH. |
| NOTE: CHECK PRODUCT APPROVAL SUBMITTED FOR MAXIMUM SIZE |
| OF WINDOW. |
| |
| E) TYPICAL WALL SECTION 3/6.1: SPECIFY HOW PROVIDING |
| THE REQUIRED FIRE RATING ON BOTH SIDES OF WALL. |
| CORRIDOR SIDE AND INTERIOR SIDE. INCLUDING THE CEILING |
| AREA. |
| |
| F) SHOW ON TYPICAL WALL SECTION 3/6.1 HOW COMPLYING |
| WITH THE FIRE BARRIER AS REQUIRED BY SEC. 706 FBC 2004. |
| |
| G) TYPICAL WALL SECTION 3/6.1 TO SHOW COMPLIANCE WITH |
| FIRE PARTITION CONTINUITY SEC. 708.4 FBC 2004. |
| |
| H) TYPICAL SECTION 3/6.1 SHOWS UL DESIGN U914. THESE IS |
| FOR A 3 HOUR FIRE RATED WALL. SPECIFICATIONS SHOWN ON |
| THIS WALL SECTION DON'T MATCH THE SPECIFICATIONS SHOWN |
| ON UL914. REVISE AS REQUIRED TO MATCH. |
| |
| I) REVISE SPOUT HEIGHT AND KNEE DETAIL. SPOUT IS 36" |
| MAX. NO MIN. |
| |
| J) INFORMATION FOR DETAIL 2/6.1 IS NOT CLEAR. |
| INFORMATION IS OVERLAPPING ON THE SHEET MARGIN LINE. |
| REVISE AS REQUIRED. |
| |
| K) TOILET ELEVATIONS: CLARIFY DIMENSION OF 33" AND 7" |
| SHOWN BY THE MIRROR AND SINK SIDE. WHERE ARE THIS |
| DIMENSIONS TAKEN FROM?. THEY DON'T WORK WITH SINK RIM |
| HEIGHT EITHER. SEE COMMENTS ON PLANS. REVISE AS |
| REQUIRED. |
| |
| 9- SHEET 7.1: |
| A) REVISE PARAPET CONSTRUCTION ON ALL WALL SECTIONS. |
| COORDINATE WITH ITEM #7A AND #7B ABOVE. |
| |
| B) REVISE ROOF SHEATHING NAILING AND SPACING ON WALL |
| SECTIONS. COORDINATE WITH ITEM #7E ABOVE. |
| |
| C) INFORMATION FOR DETAILS 10/7.1 AND DETAIL 9/7.1 IS |
| OVERLAPPING. REVISE AS REQUIRED. |
| |
| D) TYPICAL WALL SECTION 4/7.1 SPECIFIES UL ASSEMBLY |
| U914, WHICH IS FOR A 3 HOUR FIRE RATED WALL. |
| SPECIFICATIONS SHOWN ON THIS DETAIL DON'T MATCH UL 914. |
| REVISE AS REQUIRED. |
| |
| 10- SHEET SEP-1: |
| A) PROVIDE COMPLETE ENGINEERING FOR LIGHT POLES TO |
| WITHSTAND 140MPH "SUSTAINED" WIND SPEED AS REQUIRED BY |
| EXTERIOR LIGHT POLES NOTES #2 AND #5. |
| |
| B) PROVIDE SHOP DRAWINGS AND SPECIFICATIONS FOR LIGHT |
| POLES THAT MEET THE DESIGN CRITERIA. THIS INFORMATION |
| NEED TO BE REVIEWED AND APPROVED BY THE ENGINEER OF |
| RECORD PRIOR TO SUBMITTAL TO THIS OFFICE. |
| |
| C) SEPARATE PERMIT MAY BE REQUIRED FOR NEW PARKING |
| WORK. COORDINATE WITH ZONING AND ENGINEERING. |
| |
| 11- PROVIDE COMPLETE SPECIFICATIONS FROM MANUFACTURER |
| FOR TWO HOUR FIRE RATED CONCRETE BLOCK AS REQUIRED BY |
| TYPE IIIB TYPE OF CONSTRUCTION SPECIFIED ON PLANS. |
| |
| 12- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED |
| BY DCA RULE 9B-72 FOR ALL SIMPSON STRUCTURAL CONNECTORS |
| SPECIFIED ON PLANS AND DETAILS. |
| NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER |
| PAGE AND PAGE WHERE CONNECTORS ARE SHOWN. NO NEED TO |
| SUBMIT COMPLETE REPORT. THIS APPLIES TO STRUCTURAL |
| CONNECTORS ONLY. |
| |
| 13- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 14- FLAT ROOF PRODUCT APPROVAL NOA 06-0626.04 |
| SUBMITTED: SELECTED ASSEMBLY ON PAGE 11 OF 24 IS FOR AN |
| INSULATED DECK. ALSO, IT'S LIMITED BY GENERAL |
| LIMITATION #7. NEED TO PROVIDE SIGNED AND SEALED RAS |
| 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND |
| CORNER AREAS. SEE GENERAL LIMITATION #7 ON PAGE 24 OF |
| 24. |
| |
| 15- PLANS AND SECTIONS DON'T SPECIFY AN INSULATED ROOF |
| ASSEMBLY. COORDINATE AND REVISE AS REQUIRED TO MATCH |
| FLAT ROOF PRODUCT APPROVAL. |
| |
| 16- ENERGY CALCULATIONS: |
| A) NEED TO BE SIGNED AND SEALED BY THE DESIGN |
| PROFESSIONAL WHO PREPARED THEM. MAKE SURE NAME AND |
| LICENSE NUMBER OF ENGINEER IS PROVIDED. |
| |
| B) AREA DOESN'T MATCH AREA SPECIFY ON PLANS. REVISE AS |
| REQUIRED TO MATCH |
| |
| 17- ASBESTOS REPORT SUBMITTED: |
| A) REPORT NEED TO BE SIGNED AND SEALED BY THE DESIGN |
| PROFESSIONAL WHO PREPARED IT AS REQUIRED BY CHAPTER 471 |
| AND 481 OF FLORIDA STATUTE. PLEASE, MAKE SURE NAME OF |
| PROFESSIONAL AND LICENSE NUMBER IS PROVIDED AND |
| ORIGINAL SEAL AN SIGNATURE IS PROVIDED AS WELL. REPORT |
| SUBMITTED WAS NO SIGNED AND SEALED. |
| |
| B) FIRM NEEDS TO PROVIDE THE CERTIFICATE OF |
| AUTHORIZATION NUMBER IN ALL SHEETS AS REQUIRED BY SEC. |
| 61G15-23.002 AND/OR 61G1-16.004 OF FLORIDA |
| ADMINISTRATIVE CODE. |
| |
| 18- PLEASE RETURN REVIEWED SET AFTER CORRECTIONS ARE |
| DONE TO ORIGINAL DRAWINGS TO EXPEDITE REVIEW PROCESS. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |