2009-02-04 11:18:37BUILDING CHANGE OF USE/ALTERATION, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER 2004 FBC WITH 2007 REVISIONS.
  
 1- DESCRIPTION OF WORK SHOWN ON PERMIT APPLICATION
 DOESN'T MATCH INFORMATION SHOWN ON PLANS SUBMITTED.
 PLANS SHOW CHANGE OF USE FROM PARKING TO MERCANTILE.
 REVISE DESCRIPTION ON PERMIT APPLICATION AS REQUIRED TO
 MATCH PLANS.
  
 2- BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT
 FEES FOR CHANGE OF USE ARE REQUIRED. BRING BACK PALM
 BEACH COUNTY STAMPED PLANS AND COPY OF THE PAID RECEIPT
 IF FEES ARE DUE. IF THIS WAS DONE BEFORE, PLEASE GET
 THE PLANS RE-STAMPED AND BRING COPY OF PAID RECEIPT. WE
 NEED THIS INFORMATION FOR RECORD KEEPING.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 4- ACCORDING TO PROPERTY APPRAISAL WEBSITE AERIAL VIEW
 OF THE BUILDING (SEE ATTACHED COPY) AND DEFINITION FOR
 BUILDING AREA ON CHAPTER SEC. 502 OF 2004 FBC THE
 BUILDING IS TO BE CONSIDERED AS ONE BUILDING. NEED TO
 PROVIDE COMPLETE INFORMATION FOR ENTIRE BUILDING TO
 VERIFY COMPLIANCE WITH:
 A) TOTAL BUILDING AREA ALLOWED ACCORDING TO THE
 BUILDING CONSTRUCTION TYPE. PROVIDE CALCULATIONS TO
 VERIFY COMPLIANCE WITH TABLE 503 FBC 2004.
  
 B) PERCENTAGE OF OPENINGS ALLOWED, INCLUDING PROTECTED
 AND UNPROTECTED OPENINGS AS REQUIRED BY TABLE 704.8 FBC
 2004.
  
 C) SEPARATION BETWEEN OCCUPANCIES. TABLE 302.3.2 FBC
 2004.
 NOTE: TAKE INTO CONSIDERATION FIRE RATING OF DOORS AND
 WINDOWS ON WALKWAY BETWEEN THRIFT SHOP AND STORAGE.
 TABLE 704.8 FBC 2004.
  
 5- ENGINEER NEEDS TO WRITE DOWN HIS LICENSE NUMBER AS
 REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODE. PLANS ONLY SHOW THE ENGINEERING FIRM CERTIFICATE
 OF AUTHORIZATION NUMBER, NOT THE ENGINEER'S LICENSE
 NUMBER. THIS APPLIES TO TITLE BLOCK ON ALL SHEETS.
  
 6- SHEET 2.1:
 A) GENERAL NOTES ON THE BOTTOM LEFT OF SHEET DON'T
 CORRESPOND TO THIS PROJECT. THEY CORRESPOND TO AN
 EATING PLACE LIKE SUBWAY. REVISE NOTES AS REQUIRED TO
 INCLUDE ONLY THE ONES THAT PERTAIN TO THIS JOB.
  
 B) UPDATE CODES FOR THIS PROJECT. REFER TO FBC 2004
 WITH 2007 REVISIONS, NOT 2006. ALSO, THE SCOPE OF WORK
 INCLUDES CHANGE OF OCCUPANCY. SEE CHAPTER 8 OF 2004
 FLORIDA EXISTING BUILDING CODE.
  
 C) PROJECT DATA AT THIS TENANT INFORMATION: COORDINATE
 ALL INFORMATION WITH ITEM #4 ABOVE.
 IN ADDITION CLARIFY THE FOLLOWING:
 * WHERE WAS GROUP M "ORDINARY HAZARD" TERM AND STORAGE
 S-1 "ORDINARY HAZARD" TERM TAKEN FROM. WHAT DOES
 "ORDINARY HAZARD" MEANS. SPECIFY CODE SECTION OR TABLE
 WHERE THIS WAS TAKEN FROM.
  
 ** GENERAL HEIGHT AND AREA INFORMATION IS INCORRECT
 BASED ON THE TYPE OF CONSNTRUCTION IIIB. REVISE AS
 REQUIRED.
  
 *** REVISE FIRE RATED CORRIDORS INFORMATION. SEE TABLE
 1016.1 FBC 2004.
  
 **** REVISE MAXIMUM TRAVEL DISTANCE. ACCORDING TO
 CONSTRUCTION TYPE SHOWN THIS IS TYPE III UNSPRINKLERED.
  
 ***** REVISE INFORMATION GIVEN ON CONSTRUCTION
 CLASIFICATION PER TABLE 602 FBC 2004. INFORMATION IS
 NOT CLEAR, FIRE RATING IS NOT SPECIFIED AND NEED TO
 COORDINATE THIS INFORMATION WITH ITEM #4 ABOVE.
  
 ****** CLARIFY WHERE IS THE NUMBER OF PEOPLE CONSIDERED
 FOR THE STORAGE AREA TAKEN FROM. THIS NUMBER DOESN'T
 WORK WITH TABLE 1004.1.2 FBC 2004. IT CAN'T HAVE MORE
 PEOPLE THAN THAT ALLOWED BY THE TABLE.
  
 D) REVISE DESIGN PARAMETERS INFORMATION: WHERE IS
 SECTION 1609.6A-D TAKEN FROM. SEE CODE FOR CORRECT CODE
 SECTIONS TO BE REFERENCED.
  
 E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR RAMP
 HANDRAILS IN CORRIDOR BETWEEN THRIFT STORE AND STORAGE
 TO VERIFY COMPLIANCE WITH SEC. 11-4.8.5 FBC 2004.
  
 F) PROVIDE COMPLETE INFORMATION TO VERIFY IF HANDRAILS
 ARE REQUIRED OR NOT ON RAMP GOING TO THE THRIFT STORE
 BY EAST WALL SINGLE DOOR.
  
 G) LANDING ON EAST RAMP BY SINGLE ENTRY DOOR DOESN'T
 COMPLY WITH SEC. 11-4.8.4 FBC 2004. REVISE AS REQUIRED.
  
 H) MANEUVERING CLEARANCES AT DOOR LEADING TO THE WOMEN
 TOILET ROOM DOESN'T COMPLY WITH FIGURE 25 OF CHAPTER 11
 FBC 2004. PROVIDE DIMENSIONS SHOWING COMPLIANCE.
  
 I) INFORMATION ON INTERIOR WALL DETAIL AND GENERAL WALL
 LEGEND DOESN'T MATCH. REVISE STUD SPACING TO MATCH.
  
 J) PROVIDE COMPLETE CALCULATIONS SHOWING HOW THE
 DIMENSIONS FOR ALLOWED WALL OPENINGS WHERE TAKEN FROM.
 IN ADDITION. NEED TO COORDINATE THIS INFORMATION WITH
 ITEM #4 ABOVE. PROVIDE SKETCH SHOWING CONSIDERED WALL
 AREAS AND CORRESPONDING DISTANCES.
  
 K) SHOW OVERALL BUILDING FOOTPRINT. COORDINATE WITH
 ITEM #4 ABOVE.
  
 7- SHEET 5.1:
 A) PARAPET WALL DETAIL: PARAPET WALL TO HAVE THE SAME
 FIRE-RESISTANCE RATING AS THE WALL SUPPORTING IT AS
 REQUIRED BY SEC. 704.11.1 FBC 2004. REVISE AS REQUIRED.
  
 B) SHEET 2.1 SPECIFIES TYPE IIIB CONSTRUCTION TYPE.
 REVISE PARAPET CONSTRUCTION AS REQUIRED TO MATCH TYPE
 OF CONSTRUCTION SPECIFIED FOR THE BUILDING.
  
 C) PROVIDE COMPLETE TRUSS ENGINEERING PACKAGE. TRUSS
 PACKAGE NEED TO BE REVIEWED AND APPROVED IN WRITING BY
 THE ENGINEER OF RECORD PRIOR TO SUBMITTAL TO THIS
 OFFICE.
  
 D) COMPONENTS AND CLADDING PRESSURES ZONES FOR ROOF
 SCHEDULE: CLARIFY WHY SPACING FOR NAILS AT INTERMEDIATE
 SUPPORTS IS NOT GIVEN FOR ROOF ZONE #3.
  
 E) PLYWOOD ROOF SHEATHING SPECIFICATIONS SHOWN ON
 PARAPET WALL DETAIL DON'T MATCH SPECIFICATIONS SHOWN ON
 COMPONENTS AND CLADDING SCHEDULE AND ON PLYWOOD
 SHEATHING NAILING SCHEDULE NOTE AT BOTTOM RIGHT CORNER
 OF SHEET. REVISE AS REQUIRED.
  
 F) ROOF DESIGN LOADS TO MATCH LOADS SPECIFIED ON SHEET
 2.1.
  
 G) ROOF FRAMING PLAN: CLARIFY WHY NEW GUTTER BY OTHERS
 ON EXISTING HIGHER ROOF. THERE IS NOT BUILDING SECTION
 ON SHEET 7 AS SPECIFIED ON NOTE. PROVIDE ALL PERTINENT
 INFORMATION AS REQUIRED. CLARIFY IF A SEPARATE PERMIT
 WILL BE APPLIED FOR THE GUTTER.
  
 8- SHEET 6.1:
 A) COMPONENTS AND CLADDING PRESSURES ZONES FOR WALLS
 SCHEDULE: CLARIFY WHY THE NAIL SPACING IS MORE CLOSER
 TOGETHER FOR ZONE 4 THAN FOR ZONE 5.
  
 B) CLARIFY WHY THERE IS NOT NAILING SPECIFICATIONS FOR
 INTERMEDIATE SUPPORTS ON ZONE 4 OF COMPONENTS AND
 CLADDING SCHEDULE.
  
 C) STRUCTURAL DOOR BUCK DETAIL: SEE SUBMITTED PRODUCT
 APPROVAL AND REVISE DOOR BUCK DETAIL AS REQUIRED.
  
 D) SOME SIZE OF WINDOWS SHOWN ON ELEVATIONS DON'T MATCH
 SIZE OF WINDOWS SPECIFIED ON FLOOR PLAN ON SHEET 2.1.
 REVISE AS REQUIRED TO MATCH.
 NOTE: CHECK PRODUCT APPROVAL SUBMITTED FOR MAXIMUM SIZE
 OF WINDOW.
  
 E) TYPICAL WALL SECTION 3/6.1: SPECIFY HOW PROVIDING
 THE REQUIRED FIRE RATING ON BOTH SIDES OF WALL.
 CORRIDOR SIDE AND INTERIOR SIDE. INCLUDING THE CEILING
 AREA.
  
 F) SHOW ON TYPICAL WALL SECTION 3/6.1 HOW COMPLYING
 WITH THE FIRE BARRIER AS REQUIRED BY SEC. 706 FBC 2004.
  
 G) TYPICAL WALL SECTION 3/6.1 TO SHOW COMPLIANCE WITH
 FIRE PARTITION CONTINUITY SEC. 708.4 FBC 2004.
  
 H) TYPICAL SECTION 3/6.1 SHOWS UL DESIGN U914. THESE IS
 FOR A 3 HOUR FIRE RATED WALL. SPECIFICATIONS SHOWN ON
 THIS WALL SECTION DON'T MATCH THE SPECIFICATIONS SHOWN
 ON UL914. REVISE AS REQUIRED TO MATCH.
  
 I) REVISE SPOUT HEIGHT AND KNEE DETAIL. SPOUT IS 36"
 MAX. NO MIN.
  
 J) INFORMATION FOR DETAIL 2/6.1 IS NOT CLEAR.
 INFORMATION IS OVERLAPPING ON THE SHEET MARGIN LINE.
 REVISE AS REQUIRED.
  
 K) TOILET ELEVATIONS: CLARIFY DIMENSION OF 33" AND 7"
 SHOWN BY THE MIRROR AND SINK SIDE. WHERE ARE THIS
 DIMENSIONS TAKEN FROM?. THEY DON'T WORK WITH SINK RIM
 HEIGHT EITHER. SEE COMMENTS ON PLANS. REVISE AS
 REQUIRED.
  
 9- SHEET 7.1:
 A) REVISE PARAPET CONSTRUCTION ON ALL WALL SECTIONS.
 COORDINATE WITH ITEM #7A AND #7B ABOVE.
  
 B) REVISE ROOF SHEATHING NAILING AND SPACING ON WALL
 SECTIONS. COORDINATE WITH ITEM #7E ABOVE.
  
 C) INFORMATION FOR DETAILS 10/7.1 AND DETAIL 9/7.1 IS
 OVERLAPPING. REVISE AS REQUIRED.
  
 D) TYPICAL WALL SECTION 4/7.1 SPECIFIES UL ASSEMBLY
 U914, WHICH IS FOR A 3 HOUR FIRE RATED WALL.
 SPECIFICATIONS SHOWN ON THIS DETAIL DON'T MATCH UL 914.
 REVISE AS REQUIRED.
  
 10- SHEET SEP-1:
 A) PROVIDE COMPLETE ENGINEERING FOR LIGHT POLES TO
 WITHSTAND 140MPH "SUSTAINED" WIND SPEED AS REQUIRED BY
 EXTERIOR LIGHT POLES NOTES #2 AND #5.
  
 B) PROVIDE SHOP DRAWINGS AND SPECIFICATIONS FOR LIGHT
 POLES THAT MEET THE DESIGN CRITERIA. THIS INFORMATION
 NEED TO BE REVIEWED AND APPROVED BY THE ENGINEER OF
 RECORD PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 C) SEPARATE PERMIT MAY BE REQUIRED FOR NEW PARKING
 WORK. COORDINATE WITH ZONING AND ENGINEERING.
  
 11- PROVIDE COMPLETE SPECIFICATIONS FROM MANUFACTURER
 FOR TWO HOUR FIRE RATED CONCRETE BLOCK AS REQUIRED BY
 TYPE IIIB TYPE OF CONSTRUCTION SPECIFIED ON PLANS.
  
 12- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED
 BY DCA RULE 9B-72 FOR ALL SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS AND DETAILS.
 NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE WHERE CONNECTORS ARE SHOWN. NO NEED TO
 SUBMIT COMPLETE REPORT. THIS APPLIES TO STRUCTURAL
 CONNECTORS ONLY.
  
 13- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 14- FLAT ROOF PRODUCT APPROVAL NOA 06-0626.04
 SUBMITTED: SELECTED ASSEMBLY ON PAGE 11 OF 24 IS FOR AN
 INSULATED DECK. ALSO, IT'S LIMITED BY GENERAL
 LIMITATION #7. NEED TO PROVIDE SIGNED AND SEALED RAS
 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND
 CORNER AREAS. SEE GENERAL LIMITATION #7 ON PAGE 24 OF
 24.
  
 15- PLANS AND SECTIONS DON'T SPECIFY AN INSULATED ROOF
 ASSEMBLY. COORDINATE AND REVISE AS REQUIRED TO MATCH
 FLAT ROOF PRODUCT APPROVAL.
  
 16- ENERGY CALCULATIONS:
 A) NEED TO BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL WHO PREPARED THEM. MAKE SURE NAME AND
 LICENSE NUMBER OF ENGINEER IS PROVIDED.
  
 B) AREA DOESN'T MATCH AREA SPECIFY ON PLANS. REVISE AS
 REQUIRED TO MATCH
  
 17- ASBESTOS REPORT SUBMITTED:
 A) REPORT NEED TO BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL WHO PREPARED IT AS REQUIRED BY CHAPTER 471
 AND 481 OF FLORIDA STATUTE. PLEASE, MAKE SURE NAME OF
 PROFESSIONAL AND LICENSE NUMBER IS PROVIDED AND
 ORIGINAL SEAL AN SIGNATURE IS PROVIDED AS WELL. REPORT
 SUBMITTED WAS NO SIGNED AND SEALED.
  
 B) FIRM NEEDS TO PROVIDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER IN ALL SHEETS AS REQUIRED BY SEC.
 61G15-23.002 AND/OR 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 18- PLEASE RETURN REVIEWED SET AFTER CORRECTIONS ARE
 DONE TO ORIGINAL DRAWINGS TO EXPEDITE REVIEW PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712