Plan Review Notes For Permit 09010323 |
Permit Number |
09010323 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2009-05-14 13:14:26 | DENIED | | REFERENCE: | | FBC-2004 PLUMBING | | | | 1. SHTS P-3 & P-4. THE VENT FOR THE TUB/SHOWER/WATER | | CLOSET IS A DRY HORIZONTAL VENT. PER SECTION 905.4 | | EVERY DRY VENT SHALL RISE VERTICALLY TO A MINIMUM OF 6 | | INCHES ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST TRAP OR | | TRAPPED FIXTURE BEING VENTED. THE VENT SHALL RISE | | VERTICALLY TO 6 INCHES ABOVE THE TOILET FLOOD LEVEL RIM | | PRIOR TO OFFSETTING HORIZONTALLY. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|