2009-02-20 16:12:58DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHTS P-3 & P-4 PLUMBING 2ND FLOOR & SANITARY RISER
 DIAGRAM SHOWS A HORIZONTAL DRY VENT UPSTREAM OF THE TUB
 & SHOWER. THIS IS PROHIBITED BY SECTIONS 905.3 & 905.4.
 (SEE RED LINE EXAMPLE TO CORRECT VENT).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  