Plan Review Notes For Permit 09010323 |
Permit Number |
09010323 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-02-20 16:12:58 | DENIED | | REFERENCE: | | FBC-2004 PLUMBING | | | | 1. SHTS P-3 & P-4 PLUMBING 2ND FLOOR & SANITARY RISER | | DIAGRAM SHOWS A HORIZONTAL DRY VENT UPSTREAM OF THE TUB | | & SHOWER. THIS IS PROHIBITED BY SECTIONS 905.3 & 905.4. | | (SEE RED LINE EXAMPLE TO CORRECT VENT). | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|