2009-02-17 16:50:15 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| REVISIONS. |
| |
| 1- SHEET SP-1: |
| A) DESIGN CRITERIA SPECIFIES BUILDING TO BE ON EXPOSURE |
| "C", WHILE DESIGN CRITERIA ON SHEET S-1 AND SHEET S-2 |
| SPECIFIES EXPOSURE "B". REVISE AS REQUIRED TO MATCH. |
| AND, PROVIDE CORRESPONDING DESIGN PRESSURES. |
| |
| B) CLARIFY IF CONSTRUCTION TYPE IS VA OR VB. |
| |
| 2- SPECIFY TYPE OF EXISTING LOUVERS AND PROVIDE DETAILS |
| SHOWING HOW ARE THEY GOING TO BE RE-INSTALLED |
| CONSIDERING THAT NEW WINDOWS WILL BE INSTALLED ON SAME |
| OPENING TO VERIFY COMPLIANCE WITH THE DESIGN LOADS OF |
| SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) WINDOW MULLIONS. AND, CLEARLY MARK SPECIFIC MULLION |
| SIZE AND ANCHORING TO VERIFY COMPLIANCE WITH THE |
| CALCULATED DESIGN PRESSURES. |
| |
| B) ROOF TILE ADHESIVE TO BE USED. SEE PRODUCT APPROVAL |
| FOR REFERENCED INFORMATION. |
| |
| 4- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL PRODUCT |
| APPROVALS PRIOR TO SUBMITTAL TO THIS OFFICE. SEC. |
| 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 5- REVISE DETAIL 3/S-1 TO COMPLY WITH THE RISER/TREAD |
| RATIO OF SEC. R311.5.3.2 OF 2004 FLORIDA RESIDENTIAL |
| CODE. |
| |
| 6- PROVIDE SPECIFICATION FOR TONGUE AND GROOVE ROOF |
| SHEATHING FOR NEW CANOPY. SEC. R803.2.3.1 OF 2004 |
| FLORIDA RESIDENTIAL CODE. |
| |
| 7- EXTERIOR ELEVATIONS CARDINAL ORIENTATION SHOWN ON |
| SHEET D-2 DON'T CORRESPOND TO ORIENTATION SHOWN ON |
| SHEET A-3. EG: FRONT ELEVATION IS CALLED NORTH ON SHEET |
| D-2, BUT CALLED SOUTH ON SHEET A-3. REVISE ALL AS |
| REQUIRED. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |