Plan Review Notes
Plan Review Notes For Permit 09010310
Permit Number 09010310
Review Stop P
Sequence Number 2
Notes
Date Text
2009-04-01 16:28:14DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT A-101 SUBMIT DETAILS/ELEVATIONS SHOWING
 COMPLIANCE WITH THE FOLLOWING:
  
 A. DRINKING FOUNTAIN
 1. 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 ****RESPONSE NOTED, BUT COMMENT CONSERNING SECTION
 11-4.1.3(10)(A) NOT ADDRESSED.
  
 B. W/C'S
 1. 11-4.16.4 GRAB BARS (NOT SHOWN IN MEN'S TOILET
 ROOM).
 ****RESPONSE NOTED, BUT THE DEMO SHEET DOES NOT SHOW
 THE MENS TOILET ROOM AS EXISTING SO THIS IS A NEW
 TOILET ROOM AND AS SUCH PER SECTION 11-4.1.3(11) IF
 TOILET ROOMS ARE PROVIDED, THEN EACH TOILET ROOM SHALL
 COMPLY WITH SECTION 11-4.22. SECTION 11-4.1.6((1)(B).
 COMMENT NOT ADDRESSED.
  
 C. STALLS
 1. 11-4.17.3 SIZE & ARRANGEMENT EXCEPTION (1)(2) LAV
 REQUIRED IN STALL. (SEE FIGURE 30(E)).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PER
 SECTION 11-4.1.6(1)(B) IF EXISTING ELEMENTS, SPACES, OR
 COMMON AREAS ARE ALTERED, THEN EACH SUCH ALTERED
 ELEMENT, SPACE, FEATURE, OR AREA SHALL COMPLY WITH THE
 APPLICABLE PROVISIONS OF SECTION 11-4.1.1 TO SECTION
 11-4.1.3, MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. AS
 SUCH THE LAV IS REQUIRED. THE COMMENT RESPONSE
 INDICATES THAT ON PERMIT NUMBERS 07080049 & 07110548 I
 HAD COMPLETED THE REVIEWS AND THAT I HAD VERIFIED WITH
 THE BUILDING OFFICIAL. PLAN REVIEWER MIKE PERSON
 FINISHED THE REVIEW FOR PERMIT 07080049 IN WHICH I HAD
 INDICATED THE REQUIRMENT FOR THE LAV. MIKE PERSON ALSO
 DID THE REVIEW FOR PERMIT 07110548. IF THERE IS AN
 EXCEPTION TO THE REQUIREMENT PLEASE SUBMIT THE
 EXCEPTION. THE E-MAIL WAS NOT FROM ME SO I AM NOT
 FAMILIAR WITH THE E-MAIL.
  
 D. OK
  
 F. TOILET ROOMS
 1. 11-4.22.3 UNOBSTRUCTED TURNING AREA REQUIRED. (NOT
 SHOWN IN MEN'S TOILET ROOM).
 ****RESPONSE NOTED, BUT SINCE THIS IS A NEW TOILET ROOM
 IT SHALL BE ACCESSIBLE. SECTION 11-4.1.6(1)B).
  
 3. MEN'S TOILET ROOM SHALL BE ACCESSIBLE. SECTION
 11-4.1.6(1)(B).
 ****RESPONSE NOTED, BUT ALL TOILET ROOMS PROVIDED SHALL
 COMPLY WITH SECTION 11-4.22.
  
 4. A TURNING AREA IS REQUIRED AT THE KITCHENETTE.
 SECTION 11-4.2.3.
 ****RESPONSE NOTED, BUT THE TURNING AREA IS REQUIRED
 "IN" THE KITCHENETTE, NOT OUTSIDE THE KITCHENETTE.
  
 5. OK
 6. OK
 7. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  