 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE CIRCUIT NUMBERS SOR THE LIGHTING CIRCUITS
 SHOWN ON SHEET E-102. 106.3.5 FBC AS AMENDED.
  
 2} THE LPD OF 1.2 W/SQ.FT FOR THE CORRIDOR DENSITY IS
 INCORRECT PER 13-415.2.B WHICH LISTS CORRIDORS @ 0.5
 ALLOWED W/SQ.FT. SHEET E-102.
  
 3} PROVIDE A PANEL SCHEDULES FOR THE REMODEL AREA
 CIRCUITING PER 408.4 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  