Date Text
2009-02-23 15:37:182004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) ON SHEET A-6 UNDER ROOF NOTES AND TRUSS LOADING THE
 EXPOSURE CATEGORY HAS NOT BEEN CHANGED FROM 'B' TO 'C'.
 PLEASE CORRECT. FBC R301.2.1.4
  
 2) FACED BATT INSULATION CAN NOT BE INSTALLED AS SHOWN
 ON SHEET A-3. THE EXPOSED VAPOR BARRIER FACING IS
 FLAMMABLE. ALSO THE TOP CORD OF THE TRUSSES ARE 2 X 4S
 AND THE R-19 BATTS ARE 6'. PLEASE CORRECT. IF THE
 INSULATION IS INSTALLED AT THE CEILING, ATTIC
 VENTILATION WILL BE REQUIRED IN COMPLIANCE WITH FBC
 R806.1.
  
 3) THE CEILING TYPE IS SPECIFIED AS UNDER ATTIC ON THE
 ENERGY CALCULATION FORMS AND PLANS SHOW IT INSTALLED AS
 A SINGLE ASSEMBLY WITH NO ATTIC. PLEASE CORRECT. SEE
 FBC 13-604
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]