2009-01-28 07:52:21 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. | | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS | | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING | | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE | | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE | | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE | | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE | | INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN OR | | NOTE THE CODE SECTION. | | | | 2} SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | 440.14, RECEPTACLE PER 210.63 FOR THE NEW CONDENSING | | UNITS | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|