Plan Review Notes
Plan Review Notes For Permit 09010259
Permit Number 09010259
Review Stop B
Sequence Number 1
Notes
Date Text
2009-01-30 11:50:052004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) THE EXPOSURE CATEGORY IS SPECIFIED AS B ON SHEETS
 A-2 AND A-6. THE STRUCTURE IS LOCATED DIRECTLY ADJACENT
 TO EXPOSURE C TYPE TERRAIN FOR MORE THAN 600 FEET.
 THEREFORE, IT IS CONSIDERED EXPOSURE C. PLEASE REVISE.
 R301.2.1.4 EXPOSURE CATEGORY. EXPOSURE C. OPEN TERRAIN
 WITH SCATTERED OBSTRUCTIONS, INCLUDING SURFACE
 UNDULATIONS OR OTHER IRREGULARITIES, HAVING HEIGHTS
 GENERALLY LESS THAN 30 FEET (9144 MM) EXTENDING MORE
 THAN 1,500 FEET (457.2 M) FROM THE BUILDING SITE IN ANY
 QUADRANT. THIS EXPOSURE SHALL ALSO APPLY TO ANY
 BUILDING LOCATED WITHIN EXPOSURE B-TYPE TERRAIN WHERE
 THE BUILDING IS DIRECTLY ADJACENT TO OPEN AREAS OF
 EXPOSURE C-TYPE TERRAIN IN ANY QUADRANT FOR A DISTANCE
 OF MORE THAN 600 FEET (182.9 M). SHORT-TERM (LESS THAN
 TWO YEAR) CHANGES IN THE PRE-EXISTING TERRAIN EXPOSURE,
 FOR THE PURPOSES OF DEVELOPMENT, SHALL NOT BE
 CONSIDERED OPEN FIELDS. WHERE DEVELOPMENT BUILD OUT
 WILL OCCUR WITHIN THREE YEARS AND THE RESULTANT
 CONDITION WILL MEET THE DEFINITION OF EXPOSURE B,
 EXPOSURE B SHALL BE REGULATING FOR THE PURPOSE OF
 PERMITTING. THIS CATEGORY INCLUDES FLAT OPEN COUNTRY,
 GRASSLANDS AND OCEAN OR GULF SHORELINES. THIS CATEGORY
 DOES NOT INCLUDE INLAND BODIES OF WATER THAT PRESENT A
 FETCH OF 1 MILE (1.61 KM) OR MORE OR INLAND WATERWAYS
 OR RIVERS WITH A WIDTH OF 1 MILE (1.61 KM) OR MORE (SEE
 EXPOSURE D).
  
 2) PLEASE REVISE THE COMPONENT AND CLADDING PRESSURES
 TO REFLECT THE CHANGE OF EXPOSURE CATEGORY FROM B TO C.
 SEE FBC TABLE R301.2(3).
  
 3) IN THE TRUSS ANCHOR SCHEDULE ON SHEET A-6 THERE IS A
 TYPO FOR THE USP CONNECTORS. THE TALP 16 SPECIFIED IN
 THE SCHEDULE SHOULD BE TAPL 16. PLEASE CORRECT.
  
 4) ON THE ROOF FRAMING PLAN ON SHEET A-6 IT APPEARS
 THAT THE A2 AND A4 ANCHORS WERE REVERSED. THE SCHEDULE
 SPECIFIES 2 - HLTPA75 WITH A UPLIFT OF 3483 # FOR THE
 A2 AT THE HIP JACK TRUSSES AND A TAPL16 WITH UPLIFT
 1350# FOR THE A4 AT THE HIP GIRDER. THE HIGHER UPLIFT
 WILL BE ON THE GIRDER. PLEASE REVIEW.
  
 5) SHOW COMPLIANCE WITH R803.2.3.1 SHEATHING
 FASTENINGS.
 WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO
 ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON
 CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY,
 0.42 < G < 0.49 IS USED, SPACING OF RING-SHANK
 FASTENERS SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3
 FOR 130 MPH OR GREATER DESIGN WIND SPEEDS IN ACCORDANCE
 WITH FIGURE R803.2.3.1.
  
 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE GLASS
 BLOCK. DCA RULE 9B-72
  
 7) SPECIFY THE ATTACHMENT METHOD AND CORRESPONDING
 ATTACHMENT RESISTANCE MOMENT THAT WILL BE USED TO
 INSTALL THE HANSON ROOF TILE. CIRCLE THE APPROPRIATE
 ITEM ON THE ROOF TILE NOA. FBC R905.3
  
 8) SUBMIT THE MANUFACTURER'S SPECIFICATION/ LISTING FOR
 THE SPRAY FOAM INSULATION. FBC R314
  
 9) SHOW COMPLIANCE WITH R320.1 TERMITE PROTECTION SHALL
 BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES
 APPLIED TO WOOD, OR OTHER APPROVED METHODS OF TERMITE
 PROTECTION LABELED FOR USE AS A PREVENTATIVE TREATMENT
 TO NEW CONSTRUCTION (SEE SECTION 202, REGISTERED
 TERMITICIDE). UPON COMPLETION OF THE APPLICATION OF THE
 TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF
 COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT
 BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE
 FOLLOWING STATEMENT: ???THE BUILDING HAS RECEIVED A
 COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
 TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND
 LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES.???
  
 10) SPECIFY CONCRETE SLAB THICKNESS, REINFORCEMENT,
 VAPOR RETARDER, ETC. SEE FBC R506
  
 11) SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH. ALL
 EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES
 (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
  
 12) R401.4 SOIL TESTS. IN AREAS LIKELY TO HAVE
 EXPANSIVE, COMPRESSIBLE, SHIFTING OR OTHER UNKNOWN SOIL
 CHARACTERISTICS, THE BUILDING OFFICIAL SHALL DETERMINE
 WHETHER TO REQUIRE A SOIL TEST TO DETERMINE THE
 SOIL???S CHARACTERISTICS AT A PARTICULAR LOCATION. THIS
 TEST SHALL BE MADE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD. SUBMIT TWO SIGNED AND SEALED COPIES OF
 A SUBSURFACE SOILS REPORT FROM A QUALIFIED FLORIDA
 GEOTECHNICAL ENGINEER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved