Plan Review Notes For Permit 09010225 |
Permit Number |
09010225 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-01-16 10:21:37 | BUILDING PLAN REVIEW | | PERMIT: 09010225 | | ADD: 636 48TH STREET. | | CONT: GULFSTREAM ROOFING INC. | | TEL: (561)276-9500 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 1-16-09 | | REVIEW: 1ST | | ACTION: DENIED | | | | ROOFING PROCEDURE | | | | THE SQUARE FOOTAGE OF EACH ROOF PRODUCTS USED SHALL BE | | STATED ON THE PERMIT APPLICATION FORM FOR THE VALUE | | CALCULATION PURPOSES. | | | | ROOFING PERMIT; ONLY CHECKED ITEMS APPLY | | | | ____ 1) A NOTICE OF COMMENCEMENT MUST BE FILED WITH THE | | CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. | | | | _XX 2) CONTRACTOR IS TO PROVIDE THE FOLLOWING | | INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY: | | MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF | | EACH ROOF TYPE | | | | _XX 3) FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED | | IN ADDITION TO THE EVALUATION REPORT SUBMITTED, | | FAC9B72. WWW.FLORIDABUILDING.ORG | | | | _XX 4) FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY | | YOU ARE USING. ALSO INDICATE WHICH FASTENER IF THE | | OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. | | | | _XX 5) FOR THE FLAT DECK, SPECIFY THE ENHANCED | | FASTENING FOR CORNER AND PERIMETER ZONES. | | | | _XX 6) SEE PRODUCT LIMITATION #7. CALCULATIONS PREPARED | | BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF | | CONSULTANT REQUIRED FOR ENHANCED FASTENING. | | | | NOTE: NO INSTALLATION REPORT WAS SUBMITTED. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | PHONE (561)805-6726 | | FAX (561) 805-6676 | | [email protected] | | | | . | | | | |
|