2009-01-24 11:12:15 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| PLEASE ADDRESS THE FOLLOWING COMMENTS AND RESUBMIT: |
| |
| 1. ACCORDING TO THE SECTION VIEW ON PLANS, THE EXHAUST |
| FAN APPEARS TO BE DIRECTLY ADJACENT TO THE ROOF EDGE. |
| GUARDS SHALL BE PROVIDED WHERE FANS OR OTHER COMPONENTS |
| THAT REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET OF A |
| ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| SHALL EXTEND NOT LESS THAN 30 INCHES BEYOND EACH END OF |
| SUCH FAN OR COMPONENT AND THE TOP OF THE GUARD SHALL BE |
| LOCATED NOT LESS THAN 42 INCHES ABOVE THE ELEVATED |
| SURFACE ADJACENT TO THE GUARD. THE GUARD SHALL BE |
| CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A |
| 21-INCH-DIAMETER SPHERE AND SHALL COMPLY WITH THE |
| LOADING REQUIREMENTS FOR GUARDS SPECIFIED IN THE |
| FLORIDA BUILDING CODE, BUILDING IN ACCORDANCE WITH FBCM |
| 304.10. |
| |
| 2. GREASE DUCT AND FIRE WRAP ARE SHOWN PENETRATING A |
| FLOOR/CEILIGN ASSEMBLY AS IT ENTERS THE 2ND FLOOR. |
| PROVIDE A DETAIL FOR A LISTED THROUGH-PENETRATION |
| FIRESTOP SYSTEM SHOWING HOW THE PENETRATION OF THIS |
| FLOOR/CEILING ASSEMBLY IS TO BE PROTECTED IN ACCORDANCE |
| WITH FBCM 506.3.10. ALSO, FIRE WRAP MANUFACTURERS |
| INSTALLATION ISTRUCTIONS SHALL BE ON THE JOBSITE AT |
| TIME OF INSPECTION IN ACCORDANCE WITH FBCM 304.1 |
| |
| 3. WHILE THE PLANS PROVIDE WIND LOAD DATA FOR |
| ATTACHMENT OF THE EXHAUST FAN AND CURB TO BUILDING |
| STRUCTURE, NO INFORMATION WAS PROVIDED REGARDING THE |
| EXHAUST FAN REGARDING WIND RESISTANCE. EQUIPMENT AND |
| APPLIANCES WHICH ARE EXPOSED TO WIND SHALL BE DESIGNED |
| TO RESIST ANTICIPATED WIND PRESURES IN ACCORDANCE WITH |
| FBCM 301.13. PROVIDE MANUFACTURER'S DATA SHOWING THIS |
| FAN IS DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH |
| THIS SECTION. |
| |
| 4. PLANS SHOW A 20X20 LOUVER TO BE INSTALLED FOR THE |
| MAKEUP AIR FAN. LOUVERS ARE DEFINED AS PANEL WALLS PER |
| FAC RULE 9B-72 AND THEREFORE ARE SUBJECT TO THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. PROVIDE PRODUCT APPROVAL FOR |
| THE LOUVER TO BE INSTALLED PER FBCB SECTION 1609. THE |
| PRODUCT APPROVAL SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD IN ACCORDANCE WITH |
| FBCB 106.3.3. |
| |
| 5. PROVIDE SUPPORTING DOCUMENTATION SHOWING THE |
| EXISTING WOOD FLOOR TRUSSES CAN SUPPORT THE PROPOSED |
| ADDITIONAL GRAVITY LOADS ASSOCIATED WITH THE HOOD AND |
| DUCT INSTALLATIONS BEING PROPOSED IN ACCORDANCE WITH |
| THE FLORIDA BUILDING CODE, EXISTING BUILDING, SECTION |
| 607.4.1. |
| |
| 6. PROVIDE DETAIL SHOWING HOW VERTICAL GRESAE DUCT IS |
| TO BE SUPPORTED. GREASE DUCT BRACING AND SUPPORTS SHALL |
| BE OF NONCOMBUSTIBLE MATERIAL SECURELY ATTACHED TO THE |
| STRUCTURE AND DESIGNED TO CARRY GRAVITY LOADS WITHIN |
| THE STRESS LIMITATIONS OF THE FLORIDA BUILDING CODE, |
| BUILDING. BOLTS, SCREWS, RIVETS AND OTHER MECHANICAL |
| FASTENERS SHALL NOT PENETRATE DUCT WALLS IN ACCORDANCE |
| WITH FBCM 506.3.3. |
| |
| NOTE: SEPARATE PERMIT REQUIRED FOR ELECTRICAL SERVICE |
| TO NEW KITCHEN HOOD AND RELATED FANS. |
| |
| NOTE: A REVIEW BY THE CITY'S PLANNING AND ZONING |
| DEPARTMENT IS REQUIRED FOR PEOPOSED NEW ROOFTOP |
| EQUIPMENT. PLNS WILL BE ROUTED TO ZONING FOR REVIEW. |
| |