2009-01-14 15:56:48 | |
| |
| APPLICATION #09010124 ELECTRICAL PLAN REVIEW |
| 250 MURRAY ROAD 1/13/09 |
| WEST PALM BEACH, FL. |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| ALL COMMENTS RELATE TO SHEET A1, UNLESS OTHERWISE |
| NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| OTHERWISE NOTED. |
| |
| 1} THE RELOCATED ELECTRIC PANEL IN THE LAUNDRY/BATHROOM |
| IS IN VIOLATION OF 240.24(E) AND 110.26(A)(1). IN |
| DWELLING UNITS AND GUEST ROOMS OR GUEST SUITES OF |
| HOTELS AND MOTELS, OVERCURRENT DEVICES, OTHER THAN |
| SUPPLEMENTARY OVERCURRENT PROTECTION, SHALL NOT BE |
| LOCATED IN BATHROOMS. 100 BATHROOM. AN AREA INCLUDING A |
| BASIN WITH ONE OR MORE OF THE FOLLOWING: A TOILET, A |
| TUB, OR A SHOWER. |
| |
| 2} THE RECEPTACLES ON THE COUNTERTOP MUST BE GFI. |
| 210.8(A)(7) LAUNDRY, UTILITY, AND WET BAR SINKS ? WHERE |
| THE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT) OF |
| THE OUTSIDE EDGE OF THE SINK. SEE 210.8(A)(1) FOR |
| BATHROOMS. |
| |
| 3} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. SPACING ON |
| THE SOUTH AN SOUTH EAST COUNTERTOP, PENINSULAR PER |
| 21052(C)(3) AND ALL, INCLUDING THE ISLAND MUST BE GFI |
| PER 210.8. |
| |
| 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE |
| INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| [email protected] |
| |
| |