2009-01-26 11:06:45RESIDENTIAL (R3) REMODELING, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROUND WINDOW AS SHOWN ON PLANS.
  
 2- DESIGNER OF RECORD TO REVIEW AN APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 3- STRUCTURAL ENGINEER WHOSE TITLE BLOCK IS SHOWN ON
 SHEET C1 AND ALL STRUCTURAL SHEETS NEEDS TO SIGN AND
 SEAL ALL THOSE SHEETS AS REQUIRED BY SEC. 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA
 STATUTES.
  
 4- SHEET C1:
 A) THIS IS NOT AN ALTERATION LEVEL 1. SEE SEC. 303 OF
 2004 FLORIDA EXISTING BUILDING CODE AND REVISE AS
 REQUIRED.
  
 B) UPDATE GENERAL NOTE 01. CURRENT REVISIONS ARE 2007,
 NOT 2006. REVISE AS REQUIRED.
  
 5- SHEET S2:
 A) REVISE ROOF ZONE #3 SHOWN ON HIP ROOF PLAN. SEE
 FIGURE 1609.6.2.2 OF 2004 FBC AND REVISE AS REQUIRED.
  
 B) CORRECT EDITION OF REFERENCE STANDARD ACI 318 SHOWN
 ON GENERAL NOTES. SEE COMMENTS ON PLANS. SEE CHAPTER 35
 OF 2004 FBC FOR CORRECT EDITION TO BE REFERENCED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712