Plan Review Notes For Permit 09010124 |
Permit Number |
09010124 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-01-26 11:06:45 | RESIDENTIAL (R3) REMODELING, BUILDING REVIEW CHECKLIST. | | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 | | REVISIONS. | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9B-72 FOR: | | A) ROUND WINDOW AS SHOWN ON PLANS. | | | | 2- DESIGNER OF RECORD TO REVIEW AN APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | 3- STRUCTURAL ENGINEER WHOSE TITLE BLOCK IS SHOWN ON | | SHEET C1 AND ALL STRUCTURAL SHEETS NEEDS TO SIGN AND | | SEAL ALL THOSE SHEETS AS REQUIRED BY SEC. 61G15-23.002 | | FLORIDA ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA | | STATUTES. | | | | 4- SHEET C1: | | A) THIS IS NOT AN ALTERATION LEVEL 1. SEE SEC. 303 OF | | 2004 FLORIDA EXISTING BUILDING CODE AND REVISE AS | | REQUIRED. | | | | B) UPDATE GENERAL NOTE 01. CURRENT REVISIONS ARE 2007, | | NOT 2006. REVISE AS REQUIRED. | | | | 5- SHEET S2: | | A) REVISE ROOF ZONE #3 SHOWN ON HIP ROOF PLAN. SEE | | FIGURE 1609.6.2.2 OF 2004 FBC AND REVISE AS REQUIRED. | | | | B) CORRECT EDITION OF REFERENCE STANDARD ACI 318 SHOWN | | ON GENERAL NOTES. SEE COMMENTS ON PLANS. SEE CHAPTER 35 | | OF 2004 FBC FOR CORRECT EDITION TO BE REFERENCED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|