Plan Review Notes For Permit 09010115 |
Permit Number |
09010115 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-01-09 16:42:11 | 2004 FBC W/2007 REVISIONS | | REROOF | | | | DENIED BY BUILDING | | | | 1) THE PROJECT DESCRIPTION ON THE PERMIT APPLICATION | | SPECIFIES A NAILED BASE SHEET AND SELF ADHERED PLY AND | | MODIFIED CAP SHEET. THE PRODUCT APPROVAL THAT WAS | | SUBMITTED IS FOR A CONVENTIONAL BUILT-UP ROOF SYSTEM. | | SUBMIT THE CORRECT PRODUCT APPROVALS OR REVISE THE | | PERMIT APPLICATION TO MATCH THE PRODUCT APPROVALS THAT | | WERE SUBMITTED. | | | | 2) THE NOA SUBMITTED FOR THE BUILT-UP ROOF IS MISSING | | PAGE 17 WHICH CONTAINS PART OF THE INFORMATION FOR THE | | SYSTEM ON PAGE 18. | | | | 3) SPECIFY WHICH ONE OF THE FASTENING OPTIONS LISTED | | FOR THE SYSTEM WILL BE USED. | | | | 4) SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS FROM | | AN ARCHITECT OR ENGINEER FOR ENHANCED FASTENING OF THE | | BASE SHEET AS REQUIRED BY LIMITATION #7 ON PAGE 19 OF | | THE NOA. | | | | 5) SPECIFY THE AREA FOR EACH DIFFERENT TYPE OF ROOF | | COVERING ON THE APPLICATION. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|