Date |
Text |
2009-01-09 10:14:41 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN |
| IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION |
| ON THE APPLICATION, PROVIDE AN AIC RATING PER 110.9 & |
| 10. |
| |
| 2} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. THE |
| CALCULATED LOAD SHOULD INCLUDE THE TOTAL CALCULATED |
| LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS |
| USED, THE CALCULATED LOAD AFTER APPLYING DEMAND |
| FACTORS, ARTICLE 215.5 NEC 2005.*** FOR THE ENTIRE |
| SERVICE. |
| |
| 3} THERE IS NO "GROUND" PROVIDED BY FPL (SEE RISER |
| OVERHEAD) REMOVE THE #6. |
| |
| 4} 250.24(C) GROUNDED CONDUCTOR BROUGHT TO SERVICE |
| EQUIPMENT WHERE AN AC SYSTEM OPERATING AT LESS THAN |
| 1000 VOLTS IS GROUNDED AT ANY POINT, THE GROUNDED |
| CONDUCTOR(S) SHALL BE RUN TO EACH SERVICE DISCONNECTING |
| MEANS AND SHALL BE BONDED TO EACH DISCONNECTING MEANS |
| ENCLOSURE. THE GROUNDED CONDUCTOR(S) SHALL BE INSTALLED |
| IN ACCORDANCE WITH 250.24(C)(1) THROUGH (C)(3). |
| EXCEPTION: WHERE MORE THAN ONE SERVICE DISCONNECTING |
| MEANS ARE LOCATED IN AN ASSEMBLY LISTED FOR USE AS |
| SERVICE EQUIPMENT, IT SHALL BE PERMITTED TO RUN THE |
| GROUNDED CONDUCTOR(S) TO THE ASSEMBLY, AND THE |
| CONDUCTOR(S) SHALL BE BONDED TO THE ASSEMBLY |
| ENCLOSURE.*** THE RISER HAS MULTIPLE GROUND RODS. THE |
| NEUTRAL SHOULD BE GROUNDED IN THE GUTTER, A MAIN |
| BONDING JUMPER INSTALLED IN THE DISCONNECTS, AND |
| ADDITIONAL ELECTRODES ONLY AT SEPARATE STRUCTURES PER |
| 250.32 |
| |
| 5 } PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE |
| FEEDERS TO THE CABANA PANELS ON THE RISER DIAGRAM.215.5 |
| NEC. |
| |
| 6} INDICATE CONDUCTOR SIZES ON THE PANEL SCHEDULE SO |
| THAT COMPLIANCE WITH 310.16 CAN BE REVIEWED. |
| |
| 7} 210.25 COMMON AREA BRANCH CIRCUITS |
| BRANCH CIRCUITS IN DWELLING UNITS SHALL SUPPLY ONLY |
| LOADS WITHIN THAT DWELLING UNIT OR LOADS ASSOCIATED |
| ONLY WITH THAT DWELLING UNIT. BRANCH CIRCUITS REQUIRED |
| FOR THE PURPOSE OF LIGHTING, CENTRAL ALARM, SIGNAL, |
| COMMUNICATIONS, OR OTHER NEEDS FOR PUBLIC OR COMMON |
| AREAS OF A TWO-FAMILY OR MULTIFAMILY DWELLING SHALL NOT |
| BE SUPPLIED FROM EQUIPMENT THAT SUPPLIES AN INDIVIDUAL |
| DWELLING UNIT.THERE ARE TWO PANELS AND THREE UNITS. THE |
| 2ND FLOOR UNIT APPEARS HAS NO ACCESS TO THE PANEL FOR |
| THAT UNIT. PLEASE CLARIFY. |
| |
| 8} LABEL THE WATER HEATERS ON THE PLAN. 106.1 FBC |
| |
| 9} R313.1.1 RESIDENTIAL BUILDING CODE, SMOKE ALARMS |
| SHALL BE LOCATED AS REQUIRED IN NEW DWELLINGS WHEN |
| REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR. SEE |
| ARTICLE FOR COMPLETE TEXT.***LOCATE THE ALARMS ON THE |
| PLANS. |
| |
| FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE |
| FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE INDICATE |
| THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| DESIGNED.(2005 NEC) ON THE ELECTRICAL OR COVER SHEET. |
| ALSO NOTE THE 2007 REVISIONS TO THE 2004 FBC ARE IN |
| EFFECT. |
| |
| PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO |
| REVIEW COMMENTS IN WRITING. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| |
| |
| |
| |