Plan Review Notes For Permit 09010041 |
Permit Number |
09010041 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-01-23 15:50:55 | 2004 FBC W/2007 REVISIONS | | LEVEL 2 ALTERATIONS | | | | DENIED BY BUILDING | | | | 1) THE PLANS INDICATE TWO DWELLING UNITS WITHIN THE | | STRUCTURE. IF THESE ARE TWO SEPARATE DWELLING UNITS | | THEY MAY BE REQUIRED TO HAVE THEIR OWN SEPARATE STREET | | ADDRESSES. PLEASE CONTACT JOHN NGUYEN AT 561-822-1239. | | | | 2) THE DWELLING UNIT SEPARATION IS REQUIRED TO BE | | MAINTAINED. SHOW COMPLIANCE WITH R317.1 TWO-FAMILY | | DWELLINGS. DWELLING UNITS IN TWO-FAMILY DWELLINGS SHALL | | BE SEPARATED FROM EACH OTHER BY WALL AND/OR FLOOR | | ASSEMBLIES HAVING NOT LESS THAN 1-HOUR FIRE-RESISTANCE | | RATING WHEN TESTED IN ACCORDANCE WITH ASTM E 119. | | FIRE-RESISTANCE-RATED FLOOR-CEILING AND WALL ASSEMBLIES | | SHALL EXTEND TO AND BE TIGHT AGAINST THE EXTERIOR WALL, | | AND WALL ASSEMBLIES SHALL EXTEND TO THE UNDERSIDE OF | | THE ROOF SHEATHING. | | | | 3) PRODUCT APPROVALS WERE SUBMITTED FOR A PELLA | | EXTERIOR OUTSWING DOOR AND THE PLANS INDICATE THE NEW | | DOOR AS AN INSWING. PLEASE CORRECT. DCA RULE 9B-72 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|