Plan Review Notes For Permit 09010036 |
Permit Number |
09010036 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-01-15 10:41:18 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. FBC3105.3, FABRIC IS TO BE FLAME RESISTANT IN | | ACCORDANCE WITH NFPA701. FOR YOUR CONVENIENCE, I HAVE | | PRINTED THE SPEC SHEET FOR THE FABRIC SPECIFIED,, | | FIRESIST. PLEASE CONFIRM THAT THE FABRIC SPEC PRINTED | | IS THE SAME AS YOU ARE USING FOR THIS JOB. IN THE | | FUTURE, PLEASE PROVIDE DOCUMENTATION WHICH SHOWS | | COMPLIANCE WITH FBC3105.3 AS THE CERTIFICATE OF FLAME | | RESISTANCE DOES NOT SPECIFY A TEST STANDARD IN ITS | | CERTIFICATION. | | | | 2. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS | | FS481. (ELEVATIONS) | | | | 3. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT | | FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER | | (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO | | HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT | | WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE | | LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT | | BE NOTARIZED. | | | | |
|