Plan Review Notes For Permit 09010020 |
Permit Number |
09010020 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-01-05 15:45:12 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. PLEASE REVISE INSTALLATION SCHEDULE TO SPECIFY WHICH | | TYPE OF WALL CONECTION YOU PROPOSE TO INSTALL. THIS | | SHOULD CORRELATE WITH THE ANCHOR CHARTS (FOR INSTANCE, | | C1 OR C2, SEE PAGE 3). | | | | 2. SEE PAGE 3 OF THE CLEAR PANEL PRODUCT APPROVAL. | | PLEASE PROVIDE DOCUMENTATION TO SHOW THAT THE SUBSTRATE | | OF THE EXISTING HOUSE MEETS THE MINIMUM CONCCRETE | | STRENGTH OF 3350 OR 3192 PSI. ALTERNATIVELY, YOU COULD | | SPECIFY ANCHOR SPACING FOR CONCRETE BLOCK RATHER THAN | | CONCRETE. | | | | 3. PLEASE EXPLAIN SPANS. FOR INSTANCE, CLEAR PANELS, | | OPENING 2, SPECIFIES AN OPENING SIZE OF 13"X79", WXH, | | WITH A SPAN OF 20", VERTICAL INSTALLATION. THE SPAN | | SHOULD BE THE DIMENSION FROM ANCHOR TO ANCHOR; FOR A | | WALL MOUNT SHOULD BE APPROXIMATELY 86". | | | | 4. THESE COMMENTS ALSO APPLY TO THE ALUMINUM PANELS. | | |
|