Plan Review Notes
Plan Review Notes For Permit 09010020
Permit Number 09010020
Review Stop B
Sequence Number 1
Notes
Date Text
2009-01-05 15:45:12****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE REVISE INSTALLATION SCHEDULE TO SPECIFY WHICH
 TYPE OF WALL CONECTION YOU PROPOSE TO INSTALL. THIS
 SHOULD CORRELATE WITH THE ANCHOR CHARTS (FOR INSTANCE,
 C1 OR C2, SEE PAGE 3).
  
 2. SEE PAGE 3 OF THE CLEAR PANEL PRODUCT APPROVAL.
 PLEASE PROVIDE DOCUMENTATION TO SHOW THAT THE SUBSTRATE
 OF THE EXISTING HOUSE MEETS THE MINIMUM CONCCRETE
 STRENGTH OF 3350 OR 3192 PSI. ALTERNATIVELY, YOU COULD
 SPECIFY ANCHOR SPACING FOR CONCRETE BLOCK RATHER THAN
 CONCRETE.
  
 3. PLEASE EXPLAIN SPANS. FOR INSTANCE, CLEAR PANELS,
 OPENING 2, SPECIFIES AN OPENING SIZE OF 13"X79", WXH,
 WITH A SPAN OF 20", VERTICAL INSTALLATION. THE SPAN
 SHOULD BE THE DIMENSION FROM ANCHOR TO ANCHOR; FOR A
 WALL MOUNT SHOULD BE APPROXIMATELY 86".
  
 4. THESE COMMENTS ALSO APPLY TO THE ALUMINUM PANELS.
  