2009-02-24 08:54:26 | BUILDING PLAN REVIEW |
| PERMIT: 08120587 |
| ADD: 401 CLEMATIS STREET |
| CONT: MEISNER ELECTRIC |
| TEL: (561)278-8362 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 2ND |
| ACTION: DENIED |
| |
| 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| |
| 2) * NO RESPONSE NOT ADDRESSED:* PLANS SUBMITTED FOR |
| PERMIT (FIRST TIME REVIEW) AFTER JULY 1ST, 2007 SHALL |
| BE REVIEWED TO THE 2004 FBC BUILDING WITH THE 2007 |
| SUPPLEMENTS. THIS INFORMATION SHALL BE INDICATED ON THE |
| DRAWINGS. |
| |
| 3) PROVIDE THE STRUCTURAL CALCULATIONS WITH THE WIND |
| LOAD INFORMATION PER 1603.1.4. AS STATED ON THE PLANS, |
| THE BURIAL DEPTH, FOUNDATION REQUIREMENTS AND WIND LOAD |
| INFORMATION SHALL BE PROVIDED BY A STRUCTURAL ENGINEER |
| SIGN, SEAL AND DATED PER FAC 61G15-23.002. |
| NOTE: TWO DIFFERENT CALCULATION REPORTS WERE SUBMITTED |
| FOR TWO DIFFERENT POLES. IF TWO TYPES OF POLES WILL BE |
| INSTALLED AT THE LOCATION PROVIDE TWO SETS OF REPORTS |
| FOR EACH POLE. THE LIGHT POLE ON THE SITE PLAN IS |
| DIFFERENT FROM THE LIGHT POLE SPECIFICATION PROVIDED. |
| CLARIFY. |
| |
| 4) THE ORIGINAL DESIGNER SHALL APPROVE THE LIGHT POLE |
| PRIOR TO THE INSTALLATION. THE SHOP DRAWING STAMP OF |
| THE ORIGINAL DESIGN TEAM IS REQUIRED ON ALL SUBMITTALS |
| DOCUMENTS. THE SIGNATURE ON ALL DOCUMENTS SUBMITTED FOR |
| RECORD RETENTION SHALL CONTAIN THE ORIGINAL SIGNATURE |
| OF THE PERSON SIGNING EACH DOCUMENT. 106.1.3* |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| [email protected] |
| |
| |