Plan Review Notes
Plan Review Notes For Permit 08120587
Permit Number 08120587
Review Stop E
Sequence Number 1
Notes
Date Text
2009-01-06 13:40:23 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 LUMINAIRES INTENDED TO BE INSTALLED.
  
 2} A "RIGHT OF WAY" PERMIT FROM WEST PALM BEACH
 ENGINEERING DEPARTMENT IS REQUIRED PRIOR TO THE
 ELECTRICAL PERMIT BEING ISSUED. THE ENGINEERING OFFICE
 IS LOCATED @ 1000 45TH STREET, WEST PALM BEACH AND THE
 PHONE NUMBER IS561-494-1128.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  