Plan Review Notes For Permit 08120587 |
Permit Number |
08120587 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-01-12 08:53:30 | BUILDING PLAN REVIEW | | PERMIT: 08120587 | | ADD: 401 CLEMATIS STREET | | CONT: MEISNER ELECTRIC | | TEL: (561)278-8362 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: 1ST | | ACTION: DENIED | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER | | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION | | SHALL BE INDICATED ON THE DRAWINGS. | | | | 3) PROVIDE THE STRUCTURAL CALCULATIONS WITH THE WIND | | LOAD INFORMATION PER 1603.1.4. AS STATED ON THE PLANS, | | THE BURIAL DEPTH, FOUNDATION REQUIREMENTS AND WIND LOAD | | INFORMATION SHALL BE PROVIDED BY A STRUCTURAL ENGINEER | | SIGN, SEAL AND DATED PER FAC 61G15-23.002. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] | | |
|