Plan Review Notes
Plan Review Notes For Permit 08120551
Permit Number 08120551
Review Stop E
Sequence Number 1
Notes
Date Text
2009-01-14 13:03:57** DENIED REVIEW **
  
  
 1) NOTE: PLEASE UPDATE CODES FOR THE FBC 2004 W/ 2007
 REVISIONS.
 FS 553.73, FBC 106.5, 106.1.1 FOR CLARITY AND
 COORDINATION OF PLANS.
 ALSO NOTED BY THE BUILDING REVIEWER.
  
 2) NOTE: THE HATCHED AREAS ON MULTIPLE SHEETS FOR AREA
 OF SCOPE OF WORK DO NOT COORDINATE. IN FACT SEE A410,
 AND 110 AS THESE ARE CLEARLY DIFFERENT. THE SCOPE AND
 AREA IS MUCH GREATER ON SHEET 110 AND OTHER PLANS.
 PLEASE COORDINATE SO REVIEW AND PERMITTED SCOPE OF WORK
 CAN BE DETERMINED.
 FBC 106.1.1, 105.1
 NEC 2005 CHAPTERS1-4, AND OTHER POSSIBLE APPLICABLE
 CHAPTERS.
  
 3) NOTE: PLEASE PLACE NOTES AND WIRING METHODS ON PLANS
 TO MEET NEC 517 PART II.
 SCOPE DOES FALL UNDER 517 PER 517.1.
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW AREAS. 13-415.2,13-415.2.ABC.1.1,
 .1.2
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  