Plan Review Notes
Plan Review Notes For Permit 08120538
Permit Number 08120538
Review Stop P
Sequence Number 2
Notes
Date Text
2009-01-21 16:25:25PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. 802.3 802.3 WASTE RECEPTORS.
 EVERY WASTE RECEPTOR SHALL BE OF AN APPROVED TYPE. A
 REMOVABLE STRAINER OR BASKET SHALL COVER THE WASTE
 OUTLET OF WASTE RECEPTORS. WASTE RECEPTORS SHALL BE
 INSTALLED IN VENTILATED SPACES. WASTE RECEPTORS SHALL
 NOT BE INSTALLED IN BATHROOMS OR TOILET ROOMS OR IN ANY
 INACCESSIBLE OR UNVENTILATED SPACE SUCH AS A CLOSET OR
 STOREROOM. READY ACCESS SHALL BE PROVIDED TO WASTE
 RECEPTORS. (FLOOR DRAINS ARE NOT AN APPROVED WASTE
 RECEPTOR).
  
 2. OK
  
 3. OK
  
 4. OK
  
 5. OK
  
 6. NOTE: NEW WALL ON PLUMBING PLAN DOES NOT MATCH WALL
 ON A-1 - SEE BUILDING REVIEW.
 ALSO, THE ADDRESS ON P-1 IS DIFFERENT THAN A-1 - SEE
 BUILDING REVIEW.
  
 REVIEW BY LARRY WAGNER
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  