Plan Review Notes For Permit 08120538 |
Permit Number |
08120538 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-01-08 11:16:06 | PLUMBING PLAN REVIEW: | | DENIED: | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | 1. 802.3 WASTE RECEPTORS. FLOOR DRAINS SHOWN ON PLAN TO | | BE APPROVED WASTE RECEPTORS (FLOOR SINKS). | | | | 2. 905.4 VERTICAL RISE OF VENT. EVERY DRY VENT SHALL | | RISE VERTICALLY TO A MINIMUM OF 6" ABOVE THE FLOOD | | LEVEL RIM OF THE HIGEST TRAP. TWO HORIZONTAL DRY VENTS | | ARE SHOWN ON RISER DIAGRAM. | | | | 3. 1003.1 INTERCEPTORS. WHERE REQUIRED. PLEASE CONTACT | | PUBLIC UTILITIES- ENVIRNOMENTAL COMPLIANCE - HOLLY | | MCGRATH 822-2200 E-MAIL : [email protected] FOR | | DETERMINATION OF NEED FOR GREASE INTERCEPTOR. | | | | 4. 708.3.4 BASE OF STACK. A CLEANOUT | | SHALL BE PROVIDED AT THE BASE OF EACH | | WASTE OR SOIL STACK | | | | 5. FIVE FLOOR SINKS ARE SHOWN ON FLAT DRAWING. ONLY | | FOUR ARE SHOWN ON RISER DIAGRAM. | | | | REVIEW BY LARRY WAGNER | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|