2009-01-08 11:16:06PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. 802.3 WASTE RECEPTORS. FLOOR DRAINS SHOWN ON PLAN TO
 BE APPROVED WASTE RECEPTORS (FLOOR SINKS).
  
 2. 905.4 VERTICAL RISE OF VENT. EVERY DRY VENT SHALL
 RISE VERTICALLY TO A MINIMUM OF 6" ABOVE THE FLOOD
 LEVEL RIM OF THE HIGEST TRAP. TWO HORIZONTAL DRY VENTS
 ARE SHOWN ON RISER DIAGRAM.
  
 3. 1003.1 INTERCEPTORS. WHERE REQUIRED. PLEASE CONTACT
 PUBLIC UTILITIES- ENVIRNOMENTAL COMPLIANCE - HOLLY
 MCGRATH 822-2200 E-MAIL : [email protected] FOR
 DETERMINATION OF NEED FOR GREASE INTERCEPTOR.
  
 4. 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
  
 5. FIVE FLOOR SINKS ARE SHOWN ON FLAT DRAWING. ONLY
 FOUR ARE SHOWN ON RISER DIAGRAM.
  
 REVIEW BY LARRY WAGNER