2009-01-06 16:34:52 | ** DENIED REVIEW ** |
| |
| |
| |
| 1) NOTE: PLEASE SUBMIT ELECTRICAL PLANS FOR ALL NEW |
| EQUIPMENT. THE EQUIPMENT MAY NOT BE FED FROM GENERAL |
| PURPOSE RECEPTACLES OR CIRCUITS. |
| PLEASE SHOW ALL CIRCUITING ON PLANS AND COORDINATE WITH |
| A PANEL SCHEDULE TO BE SUBMITTED. |
| PLEASE BE SURE TO INCLUDE ALL NEW LOADS WITH THE |
| EXISTING LOADS FOR THE PANEL/SERVICE WHICH SUPPLIES |
| POWER TO SPACE. |
| 220, 310, 240, 408.4 ETC |
| CODE SECTIONS ARE GENERAL AS THERE WERE NO ELECTRICAL |
| PLANS SUBMITTED. |
| |
| 2) NOTE: PLEASE INDICATE THE CORRECT APPLIED LOCATION |
| OF THE PERMITTED WORK ON THE PLANS. THE LOCATION STATES |
| 307 EVERNIA HOWEVER THE APPLIED LOCATION IS 219 S |
| OLIVE. |
| INFORMATION WAS ROUTED TO THE ADDRESSING REVIEWER. ONCE |
| THE FINAL SUITE/UNIT DETERMINATION IS DONE PLEASE BE |
| SURE TO REVISED TITLE BLOCKS ACCORDINGLY. |
| FAC 61G1-16.004, FBC 106.5 |
| |
| 3) NOTE: PLEASE BE SURE TO INDICATE THE FOLLOWING CODES |
| ON PLANS FOR MINIMUM DESIGN. |
| FBC 2004W/2007 REVISIONS |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| |
| 4) NOTE: PLEASE SEE CHAPTER 13 FOR ANY PRESCRIPTIVE |
| REQUIREMENTS. |
| 13-415.1, 13-415.2. ETC |
| THERE IS NO LIGHTING SHOWN ON PLANS. |
| AS THE LAYOUT OF EQUIPMENT, COUNTERS ETC IS BEING |
| RELOCATED PLEASE SHOW NEW OR EXISTING LIGHTING. |
| |
| 5) NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9 FOR MINIMUM |
| REQUIRED LIGHTING FOR EGRESS. |
| NEW OR EXISTING? |
| |
| 6) NOTE: AS NOTED IN NOTE #1 ABOVE PLEASE BE SURE ALL |
| CONTINUOUS LOADS ARE SHOWN AT 125%. |
| 215.3,230.42, 422.13 ETC |
| |
| *** AS NO ELECTRICAL WAS SUBMITTED THERE MAY VERY WELL |
| BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |