| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC. |
| |
| 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| |
| 3} PLEASE PROVIDE A PANEL SCHEDULE SO THAT |
| BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT |
| PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC, |
| 106.3.5.4 FBC AS AMENDED. |
| |
| 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE |
| INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN. |
| |
| 5} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE |
| PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED. |
| |
| 6} INDICATE ALL REQUIRED GFI OUTLETS ON THE PLAN PER |
| 210.8 |
| |
| 7} 106.1.3 FBC AS AMENDED.LABEL THE ROOMS SO REQUIRED |
| SPACING PER 210.52, CIRCUITS PER 210.11, SMOKE |
| DETECTORS PER 313.1.1, NFPA-72 AND GFI LOCATIONS PER |
| 210.8 CAN BE REVIEWED. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |