Plan Review Notes For Permit 08120521 |
Permit Number |
08120521 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-12-30 09:51:16 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} PLANS INDICATING THE SCOPE OF WORK MUST BE SUBMITTED | | WITH THE APPLICATION. 106.1 FBC AS AMENDED. "REPAIR | | ELECTRICAL" IS STATED IN THE DESCRIPTION ON THE | | APPLICATION BUT NO PLANS WERE SUBMITTED. HAND DRAWN | | PLANS ARE NOT ACCEPTABLE FOR RECORD RETENTION OR | | CLARITY IN THE FIELD. 106.1.3 FBC AS AMENDED. | | | | 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE | | PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED. | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 | | FS, RESPECTIVELY. | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, | | IF EXEMPTIONS APPLY. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|