Plan Review Notes For Permit 08120521 |
Permit Number |
08120521 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-01-02 10:43:10 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE. | | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 507.3, | | PROVIDE CALCULATIONS. | | | | 2. ON THE FLOOR PLAN SHOW: WINDOW LOCATIONS, SIZES, | | WINDOW TYPE, ROOM DESIGNATIONS; DOOR LOCATIONS. NOTE | | EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE | | FOR BEDROOMS, FBC R310, FBC EB 505.1. THE CLEAR OPENING | | FOR BEDROOMS CANNOT BE REDUCED BY MORE THAN 5%. | | | | 3. IT APPEARS THAT OPENINGS C AND D ON THE FLOOR PLAN | | ARE DOORS; IS THIS CORRECT? PLEASE REVISE TO SPECIFY | | "DOORS" OR GRAPHICALLY SHOW A DOOR IN THESE LOCATIONS | | USING STANDARD ARCHITECTURAL GRAPHICS. FBC*106. | | | | |
|