Plan Review Notes
Plan Review Notes For Permit 08120521
Permit Number 08120521
Review Stop B
Sequence Number 1
Notes
Date Text
2009-01-02 10:43:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE.
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 507.3,
 PROVIDE CALCULATIONS.
  
 2. ON THE FLOOR PLAN SHOW: WINDOW LOCATIONS, SIZES,
 WINDOW TYPE, ROOM DESIGNATIONS; DOOR LOCATIONS. NOTE
 EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE
 FOR BEDROOMS, FBC R310, FBC EB 505.1. THE CLEAR OPENING
 FOR BEDROOMS CANNOT BE REDUCED BY MORE THAN 5%.
  
 3. IT APPEARS THAT OPENINGS C AND D ON THE FLOOR PLAN
 ARE DOORS; IS THIS CORRECT? PLEASE REVISE TO SPECIFY
 "DOORS" OR GRAPHICALLY SHOW A DOOR IN THESE LOCATIONS
 USING STANDARD ARCHITECTURAL GRAPHICS. FBC*106.
  
  