Plan Review Notes
Plan Review Notes For Permit 08120504
Permit Number 08120504
Review Stop E
Sequence Number 4
Notes
Date Text
2009-10-28 15:52:43** REDLINED PLANS. **
  
 1) 2005 NEC
  
 2) BATH CIRCUIT PER 210.52D, 210.11.C.3
  
 3) LOAD CALCULATIONS STATE ONLY ONE SMALL APPLIANCE
 CIRCUIT YET SHOWN IN CALCS. 220.53,210.11.C.1
  
 4) WATER HEATER INDICATES 40AMP OCP ON #10 AWG WHICH IS
 TOO HIGH. VIF THE KW RATING OF WATER HEATER AND CORRECT
 BRANCH CIRCUIT SIZING PER 422.13, 310.16, 240.4
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  