Plan Review Notes For Permit 08120504 |
Permit Number |
08120504 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2009-10-28 15:52:43 | ** REDLINED PLANS. ** | | | | 1) 2005 NEC | | | | 2) BATH CIRCUIT PER 210.52D, 210.11.C.3 | | | | 3) LOAD CALCULATIONS STATE ONLY ONE SMALL APPLIANCE | | CIRCUIT YET SHOWN IN CALCS. 220.53,210.11.C.1 | | | | 4) WATER HEATER INDICATES 40AMP OCP ON #10 AWG WHICH IS | | TOO HIGH. VIF THE KW RATING OF WATER HEATER AND CORRECT | | BRANCH CIRCUIT SIZING PER 422.13, 310.16, 240.4 | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|