2009-11-05 16:47:22 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW FOURTH |
| CHECKLIST. |
| REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| REVISIONS. |
| |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| UP. |
| |
| 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| 13-600 OF 2004 FBC. NEED TO PROVIDE REVISED FORM 2004R. |
| ENERGY CALCULATIONS SUBMITTED ARE FOR 2001 CODE AND |
| THESE WERE THE ONES THAT WERE REJECTED ON PREVIEWS |
| REVIEW BECAUSE OF THE WRONG CODE. |
| |
| 3- SPECIFY/CLARIFY HOW COMPLYING WITH THE EGRESS |
| REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA RESIDENTIAL |
| CODE IF THE EXISTING WINDOW CAN'T BE USED BECAUSE OF |
| BATHROOM ADDITION. (REPEAT COMMENT). SPECIFY SIZE OF |
| EXISTING EGRESS WINDOW THAT IS SHOWN NOW AND SIZE OF |
| EXISTING WINDOW TO BE BLOCKED WITH NEW BATHROOM TO |
| VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS. PLANS |
| SUBMITTED STILL DON'T SPECIFY THE SIZE OF EXISTING |
| WINDOW TO REMAIN. EGRESS REQUIREMENTS HAVE BEEN REDUCED |
| BY ELIMINATING ONE WINDOW. SEE SEC. 501.2 OF 2004 |
| FLORIDA RESIDENTIAL CODE. |
| |
| 4- SURVEY TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY |
| CHAPTER 472 (REPEAT COMMENT). SURVEYS SUBMITTED ARE |
| COPIES OF THE SIGNATURE. RESUBMIT SURVEYS WITH ORIGINAL |
| SIGNATURE. |
| |