2009-06-01 10:10:20 | *** DENIED PLANS **** | | | | ** PLANS ARE COMING BACK FOR COMMENTS FROM OTHER | | TRADES. ALSO PLANS HAVE ITEMS TAPED/ATTACHED TO SIGNED | | AND SEALED PLANS WHICH IS NOT PERMITTED. | | PLANS COULD HAVE BEEN REDLINED HOWEVER SOME ITEMS NOW | | NEED TO BE CORRECTED WHICH ARE NEW. | | | | 1) NOTE: PLEASE BE SURE THE 2005 NEC IS NOTED ON PLANS. | | | | 2) NOTE: PLEASE SEE FBC R313.2.1. PLEASE PROVIDE A | | LAYOUT FOR EXISTING DWELLING SHOWING EXISTING OR NEW | | SMOKE ALARMS MEETING CURRENT NFPA-72 2002. | | | | 3) NOTE: DEDICATED CIRCUIT FOR BATH SHALL MEET | | 210.11C3. 20AMP AND #12. PANEL SCHEDULE DOES NOT LIST. | | PLEASE SEE THAT THE PANEL SCHEDULE ONLY LIST ONE SMALL | | APPLIANCE CIRCUIT. IS THIS CORRECT? 210.11C1, 220.52. | | | | 4) NOTE: ON PLANS OTHER THAN ELECTRICAL THE NEW A/C | | SYSTEM IS GOING IN AT THIS TIME OF THE ADDITION. | | PLEASE SHOW THE REQUIRED DISCONNECT PER 441.11, 440.12. | | PLEASE ALSO SHOW THE NEW OR EXISTING GFI PER | | 210.63,210.8A3 FOR A/C EQUIPMENT | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|