Plan Review Notes
Plan Review Notes For Permit 08120504
Permit Number 08120504
Review Stop E
Sequence Number 3
Notes
Date Text
2009-06-01 10:10:20*** DENIED PLANS ****
  
 ** PLANS ARE COMING BACK FOR COMMENTS FROM OTHER
 TRADES. ALSO PLANS HAVE ITEMS TAPED/ATTACHED TO SIGNED
 AND SEALED PLANS WHICH IS NOT PERMITTED.
 PLANS COULD HAVE BEEN REDLINED HOWEVER SOME ITEMS NOW
 NEED TO BE CORRECTED WHICH ARE NEW.
  
 1) NOTE: PLEASE BE SURE THE 2005 NEC IS NOTED ON PLANS.
  
 2) NOTE: PLEASE SEE FBC R313.2.1. PLEASE PROVIDE A
 LAYOUT FOR EXISTING DWELLING SHOWING EXISTING OR NEW
 SMOKE ALARMS MEETING CURRENT NFPA-72 2002.
  
 3) NOTE: DEDICATED CIRCUIT FOR BATH SHALL MEET
 210.11C3. 20AMP AND #12. PANEL SCHEDULE DOES NOT LIST.
 PLEASE SEE THAT THE PANEL SCHEDULE ONLY LIST ONE SMALL
 APPLIANCE CIRCUIT. IS THIS CORRECT? 210.11C1, 220.52.
  
 4) NOTE: ON PLANS OTHER THAN ELECTRICAL THE NEW A/C
 SYSTEM IS GOING IN AT THIS TIME OF THE ADDITION.
 PLEASE SHOW THE REQUIRED DISCONNECT PER 441.11, 440.12.
 PLEASE ALSO SHOW THE NEW OR EXISTING GFI PER
 210.63,210.8A3 FOR A/C EQUIPMENT
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  