Plan Review Notes
Plan Review Notes For Permit 08120504
Permit Number 08120504
Review Stop E
Sequence Number 2
Notes
Date Text
2009-04-01 12:05:18REDLINED PLAN, DEDICATED CIRCUIT REQUIRED PER 210.11C3,
 MUST BE 20AMP AND #12,
 NO A/C WORK BEING DONE AT THIS TIME.