2008-12-31 10:41:39 | ** DENIED REVIEW ** |
| |
| |
| 1) NOTE: PLEASE SEE FS 481.229, 471.003. WHEN MEETING |
| EXCEPTIONS IN THE STATUTES AS MENTIONED PLANS ARE STILL |
| REQUIRED TO BE DONE BY THE DESIGN PROFESSIONAL AS |
| LISTED. |
| THE PLANS SUBMITTED DO NOT CONTAIN ANY TITLE BLOCKS, |
| PRINTED NAME, SIGNATURE, OR SIGNED AND SEALED. |
| |
| 2) NOTE: PLANS MENTIONS USE OF POSSIBLE EXISTING |
| LAUNDRY CIRCUIT OR RECEPTACLE CIRCUIT. IT IS NOT |
| PERMISSIBLE TO USE THE LAUNDRY CIRCUIT. PLEASE SEE |
| 210.52D, 210.11C2 AND 210.11C3. |
| THE LAUNDRY CIRCUIT MUST BE SEPARATE AND BE AVAILABLE |
| FOR LAUNDRY. |
| THE BATH SHALL BE DEDICATED AS LISTED IN THE ABOVE |
| SECTIONS. THERE IS TWO SEPARATE WAYS TO WIRE THE |
| BATHROOMS HOWEVER THE PLANS DO NOT INDICATE COMPLIANCE |
| WITH EITHER. |
| MUST BE 20AMP AND #12 WHEN WIRING FOR GFI. |
| |
| 2) NOTE: PLANS DO NOT INDICATE ANY NEW ELECTRICAL FOR |
| PROPOSED A/C SYSTEM. |
| PLEASE SEE 210.63, 210.8A, 440.11 FOR MISSING GFI |
| RECEPTACLES, DISCONNECTS ETC |
| |
| 3) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| THE EXISTING ELECTRICAL SERVICE WITH NEW PROPOSED A/C |
| LOADS. |
| PLEASE SEE NEC 220.83. |
| PLEASE INDICATE THE SIZE OF THE ELECTRICAL SERVICE IN |
| ORDER TO DETERMINE IF THE EXISTING IS ADEQUATE FOR NEW |
| LOADS. |
| 215.5,230.2 |
| |
| 4) NOTE: PLEASE SEE FBC 108.3 WHICH REQUIRES THE |
| APPLIED VALUE TO INCLUDE ALL LABOR, DESIGN COST, |
| MATERIALS ETC EVEN IF ANY OF THESE ARE OWNER SUPPLIED. |
| PLEASE SEE VALUATIONS BASED ON THE ADOPTED ICC |
| STANDARDS APPEARS THIS WILL CHANGE THE VALUE AS |
| APPLIED. |
| THE APPLIED SQ FT NOTES 100 SQ FT YET BASED ON THE |
| PLANS THE SQ FT IS HIGHER. |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |