Plan Review Notes
Plan Review Notes For Permit 08120504
Permit Number 08120504
Review Stop E
Sequence Number 1
Notes
Date Text
2008-12-31 10:41:39** DENIED REVIEW **
  
  
 1) NOTE: PLEASE SEE FS 481.229, 471.003. WHEN MEETING
 EXCEPTIONS IN THE STATUTES AS MENTIONED PLANS ARE STILL
 REQUIRED TO BE DONE BY THE DESIGN PROFESSIONAL AS
 LISTED.
 THE PLANS SUBMITTED DO NOT CONTAIN ANY TITLE BLOCKS,
 PRINTED NAME, SIGNATURE, OR SIGNED AND SEALED.
  
 2) NOTE: PLANS MENTIONS USE OF POSSIBLE EXISTING
 LAUNDRY CIRCUIT OR RECEPTACLE CIRCUIT. IT IS NOT
 PERMISSIBLE TO USE THE LAUNDRY CIRCUIT. PLEASE SEE
 210.52D, 210.11C2 AND 210.11C3.
 THE LAUNDRY CIRCUIT MUST BE SEPARATE AND BE AVAILABLE
 FOR LAUNDRY.
 THE BATH SHALL BE DEDICATED AS LISTED IN THE ABOVE
 SECTIONS. THERE IS TWO SEPARATE WAYS TO WIRE THE
 BATHROOMS HOWEVER THE PLANS DO NOT INDICATE COMPLIANCE
 WITH EITHER.
 MUST BE 20AMP AND #12 WHEN WIRING FOR GFI.
  
 2) NOTE: PLANS DO NOT INDICATE ANY NEW ELECTRICAL FOR
 PROPOSED A/C SYSTEM.
 PLEASE SEE 210.63, 210.8A, 440.11 FOR MISSING GFI
 RECEPTACLES, DISCONNECTS ETC
  
 3) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 THE EXISTING ELECTRICAL SERVICE WITH NEW PROPOSED A/C
 LOADS.
 PLEASE SEE NEC 220.83.
 PLEASE INDICATE THE SIZE OF THE ELECTRICAL SERVICE IN
 ORDER TO DETERMINE IF THE EXISTING IS ADEQUATE FOR NEW
 LOADS.
 215.5,230.2
  
 4) NOTE: PLEASE SEE FBC 108.3 WHICH REQUIRES THE
 APPLIED VALUE TO INCLUDE ALL LABOR, DESIGN COST,
 MATERIALS ETC EVEN IF ANY OF THESE ARE OWNER SUPPLIED.
 PLEASE SEE VALUATIONS BASED ON THE ADOPTED ICC
 STANDARDS APPEARS THIS WILL CHANGE THE VALUE AS
 APPLIED.
 THE APPLIED SQ FT NOTES 100 SQ FT YET BASED ON THE
 PLANS THE SQ FT IS HIGHER.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  