Plan Review Notes
Plan Review Notes For Permit 08120504
Permit Number 08120504
Review Stop B
Sequence Number 1
Notes
Date Text
2009-01-15 15:55:32RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD (561)233-5120) TO CHECK IF
 IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.
  
 3- DIMENSIONS SHOWN ON FLOOR PLAN AND FOUNDATION PLAN
 DON'T MATCH DIMENSIONS SHOWN ON SURVEY. REVISE AS
 REQUIRED.
  
 4- SURVEY SUBMITTED:
 A) ADDITION DIMENSIONS DON'T MATCH PLANS. REVISE AS
 REQUIRED.
  
 B) PROPERTY IS LOCATED ON FLOOD ZONE "C", NOT "X".
 REVISE AS REQUIRED. FLOOD ZONE STILL IS BASED ON FLOOD
 INSURANCE RATE MAP (FIRM) DATED MARCH 1ST OF 1979.
  
 C) SURVEY NEED ORIGINAL SIGNATURE, NOT COPY AS REQUIRED
 BY SEC. 61G17-7.0025 OF FLORIDA ADMINISTRATIVE CODE AND
 CHAPTER 472 FLORIDA STATUTE.
  
 D) GENERAL NOTE #5 STATES THAT THIS SURVEY IS NOT TO BE
 USED FOR CONSTRUCTION. NEED TO PROVIDE SURVEY THAT IS
 SUITABLE FOR CONSTRUCTION.
  
 5- PROVIDE COMPLETE DESIGN CRITERIA. SPECIFY CURRENT
 CODE 2004 FLORIDA RESIDENTIAL CODE WITH 2007 REVISIONS.
 SPECIFY ALL LIVE, DEAD, AND WIND LOADS AS REQUIRED BY
 SEC. R301 AND R301.2.1.1 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 6- NAME AND SIGNATURE OF PERSON RESPONSIBLE FOR THE
 DESIGN NEED TO BE ON ALL DRAWINGS.
  
 7- PLANS TO SPECIFY LOCATION OF VERTICAL REINFORCEMENT
 IN FILLED CELLS. SHOW ON PLANS LOCATION OF VERTICAL
 REINFORCEMENT INCLUDING THE CORNERS AND AT BOTH ENDS OF
 OPENINGS AS REQUIRED BY SECTIONS R606 AND R609 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 8- PROVIDE COMPLETE GABLE END DETAIL THAT SHOWS
 COMPLIANCE WITH SEC. R609.4 OF 2004 FLORIDA RESIDENTIAL
 CODE. PROVIDE FULL HEIGHT WALL WITH RAKE BEAM OR
 PROVIDE COMPLETE DETAIL THAT PROVIDES CONTINUOUS
 STRUCTURAL SUPPORT AND BRACING TO COMPLY WITH THIS CODE
 SECTION. SPECIFY EVERY FRAMING MEMBER AND CONNECTIONS.
  
 9- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 OF 2004 FBC.
 ***NOTE: PLEASE MAKE SURE CORRECT 2004 REVISED FORM IS
 USED. ALSO, COMPLETE ALL INFORMATION AND MAKE SURE ALL
 CORRESPONDING PARTIES SIGN AND DATE BOTTOM OF FORM.
  
 10- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED
 BY DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES.
  
 B) HURRICANE SHUTTERS. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE ATTACHED COPY. ALSO, CLEARLY
 MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING CONDITIONS
 (EG: WALL MOUNTED, BUILD OUT, ETC.) AND SPECIFIC ANCHOR
 TYPE AND SPACING TO BE USED.
  
 C) ALL SIMPSON OR USP STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND DETAILS.
 NOTE: PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING THE CONNECTOR.
  
 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 12- OWES $1.30 FOR RADON FEES AS REQUIRED BY CHAPTER
 10D-91 OF FLORIDA ADMINISTRATIVE CODE SUBPART B.
  
 13- SHEET 1:
 A) *SPECIFY 2 LAYERS OF WATER RESISTANT BARRIER OVER
 FRAME CONSTRUCTION AS REQUIRED BY SEC. R703.6.3 OF 2004
 FLORIDA RESIDENTIAL CODE.
 **CLARIFY HOW IS THE 5/8" STUCCO ON SELF FURRING PAPER
 BACKED LATH ATTACHED TO THE CONCRETE BLOCK.
 ***MIN. THICKNESS OF STUCCO ON FRAME CONSTRUCTION IS
 7/8" AS REQUIRED BY ASTM C926 AND ASTM C-1063. REVISE
 AS REQUIRED.
  
 B) SPECIFY CALCULATED OPENINGS DESIGN PRESSURES AS
 REQUIRED BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) SPECIFY/CLARIFY HOW COMPLYING WITH THE EGRESS
 REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA RESIDENTIAL
 CODE IF THE EXISTING WINDOW CAN'T BE USED BECAUSE OF
 BATHROOM ADDITION.
  
 D) SPECIFY SAFETY GLASS FOR WINDOW BY TUB AREA AS
 REQUIRED BY SEC. R308.4 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 E) SEE COMMENTS ON PLANS AND RETURN REVIEWED SET OF
 PLANS AFTER CORRECTIONS ARE DONE TO ORIGINAL DRAWINGS.
  
 F) SURVEY CAN'T BE COPIED BECAUSE OF COPYRIGHT ISSUES.
 REMOVE SURVEY INFORMATION. DRAWINGS TO SHOW SITE PLAN,
 NOT COPY OF SURVEY. BESIDES THIS SURVEY CAN'T BE USED
 FOR CONSTRUCTION. SEE NOTE #5 ON SURVEY.
  
 G) ROOF FRAMING PLAN: SPECIFY THE CALCULATED UPLIFT
 LOADS AND SPECIFIC CONNECTORS AS REQUIRED TO VERIFY
 COMPLIANCE WITH SEC. R301 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 H) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS SHOWING
 HOW JOINING THE NEW ADDITION TO THE EXISTING BUILDING
 AT ROOF AREA AND WALL AREA.
 ALSO, FOUNDATION PLAN TO SPECIFY HOW LONG AND HOW MUCH
 EMBEDMENT IS REQUIRED FOR #5 DOWELS SPECIFIED TO
 CONNECT NEW CONCRETE SLAB TO EXISTING.
  
 14- SHEET 2:
 A) BUILDING SECTION:
 *SPECIFY TWO LAYERS OF VAPOR BARRIER ON FRAMED
 CONSTRUCTION. SEC. R703.6.3 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 **CLARIFY WHY KNEE WALL SHOWS ONLY ONE TOP PLATE IF
 THIS IS A BEARING WALL?. SEE CHAPTER 6 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 ***SPECIFY ALL STRUCTURAL CONNECTORS TO SHOW COMPLIANCE
 WITH THE CONTINUOUS LOAD PATH OF SEC. R601.2 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 ****SPECIFY R-VALUES ON CEILING AND WALLS. COORDINATE
 WITH THE ENERGY CALCULATIONS.
  
 *****SPECIFY HOW LON ARE THE BOLTS SPECIFIED TO HOLD
 THE 2X8 WOOD PLATE.
  
 ******SPECIFY HOW ARE THE 2X8 ROOF RAFTERS JOINED TO
 THE 2X6 CEILING JOISTS.
  
 15- DESIGNER TO REVIEW COMMENTS SHOWN ON REVIEWED SET
 OF PLANS AND RETURN REVIEWED SET AFTER CORRECTIONS ARE
 DONE TO THE ORIGINAL DRAWINGS TO EXPEDITE REVIEW
 PROCESS AND MAKE SURE ALL COMMENTS ARE ADDRESSED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712