2009-01-09 14:28:18 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHT P-101 THE ENGINEERING FIRM AND THE ARCHITECTURAL |
| FIRM SHALL INDICATE THE CERTIFICATE OF AUTHORIZATION |
| NUMBER, (BUSINESS NUMBER), IN THE TITLE BLOCK. FAC |
| 61G15-23.002(2), 61G1-16.004(2) & FS 471.025, 481.219 & |
| 481.2055. PLEASE INDICATE BOTH NUMBERS IN TITLE BLOCK. |
| (SEE ATTACHED SHEETS FROM FLORIDA STATE DBPR WEBSITE |
| FOR CORRECT NUMBERS). |
| |
| 2. SHT P-101 WITH THE LAVS BEING DELETED ON THE VENT |
| STACK FOR THE WATER CLOSETS, A CLEANOUT IS REQUIRED ON |
| THE VENT STACK. SECTION 708.3.4. PLEASE INDICATE A |
| CLEANOUT ON THE VENT PIPE. THE SIZE OF THE CLEANOUT |
| SHALL BE THE SAME NOMINAL SIZE AS THE PIPE THEY SERVE |
| PER SECTION 708.7. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |