Plan Review Notes
Plan Review Notes For Permit 08120480
Permit Number 08120480
Review Stop B
Sequence Number 1
Notes
Date Text
2009-01-12 16:57:342004 FBC W/2007 REVISION
 ADDITION
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 3) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY CALCULATION FORM. FBC 13-6.
  
 4) THE MINIMUM WALL INSULATION IS R-5 PER ENERGY CALC.
 FORM. REVISE WALL SECTION. FBC 13-602.1.C.1.2
  
 5) SHOW COMPLIANCE WITH R311.4.3 LANDINGS AT DOORS.
 THERE SHALL BE A FLOOR OR LANDING ON EACH SIDE OF EACH
 EXTERIOR DOOR.
 EXCEPTION: WHERE A STAIRWAY OF TWO OR FEWER RISERS IS
 LOCATED ON THE EXTERIOR SIDE OF A DOOR, OTHER THAN THE
 REQUIRED EXIT DOOR, A LANDING IS NOT REQUIRED FOR THE
 EXTERIOR SIDE OF THE DOOR.
 THE FLOOR OR LANDING AT EXTERIOR DOORS REQUIRED BY
 SECTION R311.4.1 SHALL NOT BE REQUIRED TO COMPLY WITH
 THIS REQUIREMENT BUT SHALL HAVE A RISE NO GREATER THAN
 THAT PERMITTED IN SECTION R311.5.3.
 EXCEPTION: THE LANDING AT AN EXTERIOR DOORWAY SHALL NOT
 BE MORE THAN 7? INCHES (196 MM) BELOW THE TOP OF THE
 THRESHOLD, PROVIDED THE DOOR, OTHER THAN AN EXTERIOR
 STORM OR SCREEN DOOR DOES NOT SWING OVER THE LANDING.
 THE WIDTH OF EACH LANDING SHALL NOT BE LESS THAN THE
 DOOR SERVED. EVERY LANDING SHALL HAVE A MINIMUM
 DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE
 DIRECTION OF TRAVEL.
  
 6) IN ORDER TO PROVIDE AIR FLOW TO THE SPACES BETWEEN
 RAFTERS A CONTINUOUS EAVE VENT WILL BE REQUIRED. PLEASE
 REVISE WALL SECTION. SEE FBC R806.1 VENTILATION
 REQUIRED. ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES
 FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO THE
 UNDERSIDE OF ROOF RAFTERS SHALL HAVE CROSS VENTILATION
 FOR EACH SEPARATE SPACE BY VENTILATING OPENINGS
 PROTECTED AGAINST THE ENTRANCE OF RAIN. VENTILATING
 OPENINGS SHALL BE PROVIDED WITH CORROSION-RESISTANT
 WIRE MESH, WITH 1/8 INCH (3.2 MM) MINIMUM TO 1/4 INCH
 (6.4 MM) MAXIMUM OPENINGS.
  
 7) SPECIFY THE REQUIRED BEARING CAPACITY OF THE SOIL
 BASED ON THE GRAVITY DESIGN LOADS OF THE ADDITION.
 R401.2
  
 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS. ONLY ONE OF
 EACH WAS SUBMITTED. FBC 106.1* CITY AMENDMENTS.
  
 9) ON THE PRODUCT APPROVAL FOR THE GAF BUILT-UP ROOF
 SYSTEM, SPECIFY WHICH ONE OF THE FASTENING OPTIONS FOR
 THE NON-INSULATED WOOD DECK ON PAGE 17 OF THE NOA WILL
 BE USED. ALSO SUBMIT TWO COPIES OF SIGNED AND SEALED
 RAS 117 CALCULATIONS FOR ENHANCED FASTENING FROM AN
 ARCHITECT OR ENGINEER AS REQUIRED BY LIMITATION NUMBER
 7 ON PAGE 19 OF THE NOA. FBC R301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW