2009-03-25 14:56:40 | PLANS ROUTED TO DOUG WISE'S OFFICE. THERE IS A NEW C-3 |
| WHICH PREVIOUSLY HAD ZONING AND ENGINEERING STAMPS. |
2009-03-25 14:55:48 | |
| **** PROVISO *** |
| |
| ** THIS PROVISO HAS BEEN ISSUED TO PROJECT WITH THE |
| FOLLOWING CONDITIONS. ALL ITEMS IN NOTES BELOW MUST BE |
| SUBMITTED, REVIEWED AND STAMPED WITH A PASSED STATUS |
| BEFORE INSTALLATION OF ELECTRICAL EQUIPMENT OR |
| INSPECTIONS. |
| ANY INSTALLATION OF EQUIPMENT OR INSPECTIONS IN WHICH |
| THE NOTES HAVE NOT BEEN ADDRESSED MAY CREATE A DELAY IN |
| THE PROJECT OR REMOVAL OF INSTALLED EQUIPMENT. THIS |
| WOULD BE AT THE SOLE RESPONSIBILITY AND EXPENSE OF THE |
| CONTRACTORS INVOLVED WITH PROJECT. |
| |
| 1) NOTE: THIS IS THE *THIRD* REQUEST FOR THE |
| MANUFACTURES SPECS/CUT SHEETS ON THE TWO PROPOSED MTS |
| PANELS/DEVICES AS SHOWN ON RISER. THE POWER PROTECTION |
| SPECS WERE SUBMITTED WITH LISTING AS UL 891. THIS DOES |
| NOT PROVIDE ANY INFORMATION FOR LISTING OF TRANSFER |
| EQUIPMENT. |
| THERE ARE NO SUBMITTALS IN PACKAGE FOR ANY OF THE OTHER |
| EQUIPMENT AS REQUESTED. THERE IS HOWEVER SPECS FOR THE |
| METER CENTER AND OTHER EQUIPMENT WHICH WAS NEVER |
| REQUESTED ON ANY OF THE PREVIOUS REVIEWS. |
| 702.6, 701.7, 110.3, 90.7 ETC |
| |
| 2) NOTE: THE LIGHTING DETAILS ON SHEET E-9 WAS NOT |
| REVISED TO SHOW LIGHTING BEING FED TO NEW HOUSE PANEL |
| AT THE EQUIPMENT/STRUCTURE LOCATION. NO LIGHTING SHALL |
| BE FED FROM HOUSE PANEL AT OFFICE BUILDING. |
| THE OVER CURRENT PROTECTION AND CONDUCTORS SHOWN ON E-9 |
| ARE ALSO NOT THE SAME AS THE NEW ON E-9. PLEASE |
| COORDINATE AND REVISE ALL AS NEEDED. |
| AS REQUESTED ON PREVIOUS REVIEWS. PLEASE SHOW LOCATIONS |
| OF ALL LIGHTING FIXTURES. PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND BE SURE THIS INFORMATION IS COORDINATED WITH |
| PANEL SCHEDULES. |
| 408.4, 310.16, 240.4 ETC |
| |
| 3) NOTE: PLEASE BE SURE TO INDICATE THE AIC RATINGS FOR |
| ALL EQUIPMENT ON THE RISER/PLANS. ALL EQUIPMENT SHALL |
| BE RATED FOR THE AVAILABLE FAULT CURRENT WHETHER FROM |
| THE UTILITY TRANSFORMER OR ANY FUTURE GENERATORS. 110.9 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION AS A REVISION |
| BEFORE INSPECTIONS AND INSTALLATION. |
| IF THERE ARE ANY QUESTIONS OR IF ANY OF ABOVE COMMENTS |
| ARE NOT TYPED IN A CLEAR MANNER, PLEASE DO NOT HESITATE |
| IN CONTACTING THIS REVIEWER. |
| |
| DEWEY PALMER |
| BUILDING PLANS EXAMINER II/ ELECTRICAL |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |