Plan Review Notes
Plan Review Notes For Permit 08120427
Permit Number 08120427
Review Stop B
Sequence Number 3
Notes
Date Text
2009-03-13 11:44:18BUILDING PLAN REVIEW
 PERMIT: 081204427
 ADD: 8132 OKEECHOBEE BLVD
 CONT: REGENCY COMMUNICATIONS
 TEL: (954)868-4657
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 MARCH 13/2009
  
 BUILDING PROVISO:
  
 ROOFING PREMIT TO BE UNDER A SEPERATE PERMIT BY A FL
 CERTIFIED OR REGISTERED CONTRACTOR, PROVIDE 2 COPIES OF
 PRODUCT APPROVAL, NOTE MOST PRODUCT APPROVALS FOR FLAT
 ROOFS WITH A NAILABLE SYSTEM ONLY HAVE 45 TO 60 PSF.
 CIRCLE WHICH SUB-SYSTEM TO BE INSTALLED. IF LOW
 PRESSURES IN ZONE 2 AND 3 SEE IF APPROVAL ALLOWS
 ENHANCED FASTENING, AND IF SO, THE RAS 117 CALCULATION
 NEEDS TO BE COMPLETED BY A ENGINEER OR ARCHITECT.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  