2009-03-13 11:09:57 | ** DENIED RE-SUB ** |
| |
| |
| 1) NOTE: PER COMMENTS ON THE PREVIOUS REVIEW. PLEASE |
| ADJUST THE VALUE FOR THE COMPLETE SCOPE OF WORK |
| INCLUDING, DESIGN FEES, ALL LABOR, ALL MATERIALS AND |
| ALL EQUIPMENT WHETHER OR NOT ANY OF THESE ITEMS ARE |
| OWNER SUPPLIED AND NOT PROVIDED BY THE CONTRACTOR. |
| SCOPE OF WORK ON PROJECT INCLUDES 100FT FLAG POLE |
| TOWER, BASE, ALL ELECTRICAL EQUIPMENT FOR SERVICE, |
| CABINETS, FOUNDATION, WALLS AND FOUNDATION FOR WALLS, |
| ELECTRICAL SERVICE FROM FPL ETC. |
| THE ADJUSTED VALUE FROM $80K, TO $125K IS STILL LOW. AS |
| MENTIONED PREVIOUSLY ALL EQUIPMENT, LABOR, MATERIALS, |
| DESIGN COST ETC SHALL BE INCLUDED. |
| VALUE CAN BE ASSESSED USING THE ADOPTED GUIDES AND |
| VALUES PUBLISHED. |
| FBC 108.3 |
| |
| 2) NOTE: PLEASE INCLUDE THE EQUIPMENT MANUFACTURES |
| SPECS/CUT SHEETS FOR THE TRANSFER EQUIPMENT. SOME |
| MANUFACTURES EQUIPMENT SPECS/CUT SHEETS WERE SUBMITTED |
| HOWEVER NOTHING SPECIFIC TO THE TRANSFER EQUIPMENT AND |
| ANY 1008 LISTING. |
| 90.7, 110.3, 701.7 |
| |
| 3) NOTE: PLEASE PROVIDE INFORMATION ON THE CIRCUITING |
| AND INFORMATION ON LIGHTING FIXTURES ON THIS STRUCTURE |
| WHICH IS NOT PART OF THE BASE BUILDING. THE PLANS ONLY |
| NOTE AN EXISTING HOUSE PANEL. |
| NO, GROUNDING INFORMATION ON CIRCUITING FOR THESE |
| FIXTURES, NO DISCONNECTING MEANS, AND NO FIXTURE |
| INFORMATION. WHERE IS CIRCUITING, LOADS ETC IS |
| PROVIDED. |
| IF THIS IS LEGALLY LEASED SPACE THE LIGHTING FIXTURES |
| NEED TO COME FROM THIS SERVICE AND EQUIPMENT. PLANS |
| HAVE A WHOLE NEW SERVICE AND TRANSFORMER WHICH IS A |
| SEPARATELY DERIVED SYSTEM. IF THIS IS ONE STRUCTURE |
| BEING FED FROM TWO COMPLETELY DIFFERENT SERVICES THEN |
| BONDING OF SERVICES, GROUPING OF MAINS/DISCONNECTING |
| MEANS ETC NEEDS TO BE ADDRESSED. THERE IS A WAY TO |
| ADDRESS THIS HOWEVER PLEASE CALL TO GO OVER. |
| 250.50,250.20,250.32,225.31-225.39,220,408.4, 310.16, |
| 240.4 ETC. |
| THIS CAME UP IN A PREVIOUS CONVERSATION WITH DESIGNER |
| EVEN AS IT WAS NOT SPECIFICALLY GONE OVER IN PREVIOUS |
| COMMENTS. |
| |
| 4) NOTE: TITLE SHEET DOES LIST AN E-1 TO BE IN SET |
| HOWEVER NOT E-1 IS IN EITHER SET. |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |