Plan Review Notes
Plan Review Notes For Permit 08120427
Permit Number 08120427
Review Stop E
Sequence Number 2
Notes
Date Text
2009-03-13 11:09:57** DENIED RE-SUB **
  
  
 1) NOTE: PER COMMENTS ON THE PREVIOUS REVIEW. PLEASE
 ADJUST THE VALUE FOR THE COMPLETE SCOPE OF WORK
 INCLUDING, DESIGN FEES, ALL LABOR, ALL MATERIALS AND
 ALL EQUIPMENT WHETHER OR NOT ANY OF THESE ITEMS ARE
 OWNER SUPPLIED AND NOT PROVIDED BY THE CONTRACTOR.
 SCOPE OF WORK ON PROJECT INCLUDES 100FT FLAG POLE
 TOWER, BASE, ALL ELECTRICAL EQUIPMENT FOR SERVICE,
 CABINETS, FOUNDATION, WALLS AND FOUNDATION FOR WALLS,
 ELECTRICAL SERVICE FROM FPL ETC.
 THE ADJUSTED VALUE FROM $80K, TO $125K IS STILL LOW. AS
 MENTIONED PREVIOUSLY ALL EQUIPMENT, LABOR, MATERIALS,
 DESIGN COST ETC SHALL BE INCLUDED.
 VALUE CAN BE ASSESSED USING THE ADOPTED GUIDES AND
 VALUES PUBLISHED.
 FBC 108.3
  
 2) NOTE: PLEASE INCLUDE THE EQUIPMENT MANUFACTURES
 SPECS/CUT SHEETS FOR THE TRANSFER EQUIPMENT. SOME
 MANUFACTURES EQUIPMENT SPECS/CUT SHEETS WERE SUBMITTED
 HOWEVER NOTHING SPECIFIC TO THE TRANSFER EQUIPMENT AND
 ANY 1008 LISTING.
 90.7, 110.3, 701.7
  
 3) NOTE: PLEASE PROVIDE INFORMATION ON THE CIRCUITING
 AND INFORMATION ON LIGHTING FIXTURES ON THIS STRUCTURE
 WHICH IS NOT PART OF THE BASE BUILDING. THE PLANS ONLY
 NOTE AN EXISTING HOUSE PANEL.
 NO, GROUNDING INFORMATION ON CIRCUITING FOR THESE
 FIXTURES, NO DISCONNECTING MEANS, AND NO FIXTURE
 INFORMATION. WHERE IS CIRCUITING, LOADS ETC IS
 PROVIDED.
 IF THIS IS LEGALLY LEASED SPACE THE LIGHTING FIXTURES
 NEED TO COME FROM THIS SERVICE AND EQUIPMENT. PLANS
 HAVE A WHOLE NEW SERVICE AND TRANSFORMER WHICH IS A
 SEPARATELY DERIVED SYSTEM. IF THIS IS ONE STRUCTURE
 BEING FED FROM TWO COMPLETELY DIFFERENT SERVICES THEN
 BONDING OF SERVICES, GROUPING OF MAINS/DISCONNECTING
 MEANS ETC NEEDS TO BE ADDRESSED. THERE IS A WAY TO
 ADDRESS THIS HOWEVER PLEASE CALL TO GO OVER.
 250.50,250.20,250.32,225.31-225.39,220,408.4, 310.16,
 240.4 ETC.
 THIS CAME UP IN A PREVIOUS CONVERSATION WITH DESIGNER
 EVEN AS IT WAS NOT SPECIFICALLY GONE OVER IN PREVIOUS
 COMMENTS.
  
 4) NOTE: TITLE SHEET DOES LIST AN E-1 TO BE IN SET
 HOWEVER NOT E-1 IS IN EITHER SET.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  