2009-01-05 17:02:41 | ** DENIED REVIEW ** |
| |
| |
| |
| 1) NOTE: THE VALUE FOR THE SCOPE OF WORK AS APPLIED IS |
| EXTREMELY LOW. THE SCOPE AS STATED ON THE PERMIT |
| APPLICATION IS TO INCLUDE ALL LABOR, ALL MATERIALS, ALL |
| EQUIPMENT; ALL DESIGN COST ETC EVEN IF ANY OF THESE |
| ITEMS ARE OWNER SUPPLIED. THE EQUIPMENT AND MATERIALS |
| ON PLANS ALONE IS GREATER THAN THE APPLIED VALUE. |
| FBC 108.3. |
| |
| 2) NOTE: PLEASE PROVIDE MANUFACTURE SPECS/CUT SHEETS |
| FOR THE NEW SERVICE EQUIPMENT AND PROPOSED TRANSFER |
| DEVICE. 702.6, 110.3, 90.7 |
| ALL EQUIPMENT MUST BE LISTED BY A NRTL. |
| THERE ARE MANY DEVICES ON THE MARKET WHICH ARE NOT |
| LISTED AS TRANSFER EQUIPMENT. |
| |
| 3) NOTE: PLEASE PROVIDE THE FOLLOWING MINIMUM CODES TO |
| BE STATED ON PLANS. |
| 2005 NFPA-70 |
| 2004 FBC W/ 2007 REVISIONS. |
| |
| 4) NOTE: THERE ARE SEVERAL REFERENCES ON PLANS TO |
| *EXISTING* CMU WALL, OR *EXISTING* PANEL HOWEVER ALL OF |
| THESE ITEMS ARE NEW PROPOSED SCOPE OF WORK BASED ON THE |
| SUBMITTED PLANS. |
| THESE ITEMS CAN NOT ALREADY EXIST. |
| PLEASE COORDINATE PLANS FOR ALL NEW SCOPE OF WORK. |
| NEC, 240,220,408,300 ETC. NOTED FOR COMMON CODES. |
| FBC 106.1.1, NOTED FOR COORDINATION OF PLANS. |
| |
| 5) NOTE: WALL FOUNDATION STEEL TO BE PART OF THE |
| GROUNDING ELECTRODE SYSTEM. 250.50 |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |