Plan Review Notes
Plan Review Notes For Permit 08120427
Permit Number 08120427
Review Stop B
Sequence Number 1
Notes
Date Text
2009-01-12 10:21:56BUILDING PLAN REVIEW
 PERMIT: 081204427
 ADD: 8132 OKEECHOBEE BLVD
 CONT: REGENCY COMMUNICATIONS
 TEL: (954)868-4657
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) I INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) PLEASE CORELATE THE PERMIT APPLICATION, AND PLANS AS
 TO WHAT WORK WILL BE REVIEWED UNDER THIS PERMIT. THE
 PERMIT APPLICATION INDICATES THE CELL TOWER (FLAG POLE)
 AS WELL AS THE T-MOBILE EQUIPMENT ARE TO BE PART OF
 THIS PERMIT PACKAGE .THE COVER SHEET INDICATE THE SCOPE
 OF WORK TO INCLUDE THE INSTALLLATION OF NEW CONCEALMENT
 POLE WITH NEW CMU WALLED ENCLOSURE AND CONNECTIONS TO
 POWER AND TELECOMMUNICATIONS. THROUGHOUT THE PLANS
 PLANS INDICATE TO BE DESIGNED BY OTHERS, 100' CELL
 TOWER- FLAG POLE. THERE IS NO FOUNDATION NOR CELL TOWER
 INFORMATION WITHIN THIS SET OF PLANS, IS THIS TO BE
 PART OF THIS PERMIT? ADDITIONAL INFORMATION REQUIRED.
 106.1.2.
  
 2A) LOW VALUE FOR THE DESRIPTION OF WORK LISTED ON THE
 PERMIT APPLICATION.W P B ADMINISTRTIVE CODE 108.2
 SCHEDULE OF PERMIT FEES. ON BUILDINGS, STRUCTURES,
 ELECTRICAL, GAS, MECHANICAL, AND PLUMBING SYSTEMS OR
 ALTERATIONS REQUIRING A PERMIT, A FEE FOR EACH PERMIT
 SHALL BE PAID AS REQUIRED, IN ACCORDANCE WITH THE
 SCHEDULE ESTABLISHED BY THE APPLICABLE GOVERNING
 AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) SHEET C-3 ALSO INDICATES THE USE OF 5'-0"X8'-0"
 CONCRETE/FIBERCRETE EQUIPMENT PADS.ASHEET C-8 DOES
 INDICATE THE USE OF EITHER A CONCRETE OR FIBERCRETE TO
 BE USED AS A ALTERNATE. PLEASE PROVIDE
 A MINIMUM FINISH ELEVATION FOR THESE SLABS, IT APPEARS
 THAT THIS AREA IS LOCATED WITHIN A AH17 FLOOD ZONE THE
 MINIMUM SLAB HEIGHT IS 17'-6". PROOF OF MINIMUM FLOOD
 ELEVATION WILL REQUIRED BEFORE A CERTIFICATE OF
 ELEVATION IS TO BE PROVIDED.FBC BUILDING 3110.1.2 /
 CITY OF WPB CODE OF ORDINANCES SECTION 94-546.
 STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 3B) C-8 DOES INDICATE TYPE OF SLAB BUT NO INFORMATION
 IS PROVIDED FOR ATTACHMENT OF EQUIPMENT TO SLABS.
 1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT AND
 SLIDDING.
  
 3C) NO FOUNDATION OR TOWER DESIGN WAS SUBMITTED FOR THE
 CELL PHONE TOWER ,TO COMPLY WITH 1609.1.3 ANCHORAGE
 AGAINST OVERTURNING, UPLIFT AND SLIDDING AND 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  