2009-03-31 10:31:06 | BUILDING PLAN REVIEW |
| PERMIT: 08120369 |
| ADD: 100 N CLEMATIS ST |
| CONT: CATALFUMO |
| TEL: (561)282-8265 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| APRIL 1/ 2009 |
| |
| ARCHITECT: STEPHEN BORUFF |
| STEPHEN L. BORUFF, AIA |
| ARCHITECTS+ PLANNERS, INC. |
| |
| STRUCTURAL ENGINEER: TOLLIVER J. FRAZIER |
| ONM&J STRUCTURAL ENGINEERS |
| |
| |
| BUILDING PROVISO: |
| |
| |
| 1) ROOFING SYSTEMS: |
| ROOF INSULATION REVIEW THE MINIMUM THICKNESS FOR A 20.4 |
| R-VALUE SEE ENERGY INPUT DATA REPORT |
| PRODUCT APPROVAL NOA 07-0228.04 |
| DECK TYPE 21: STEEL INSULATED |
| DECK DESCRIPTION 18-22 GAUGE TYPE B |
| SYSTEM TYPE B(1) |
| MAXIMUM DESIGN PRESSURE -75 PSF LIMITATION # 7 ALLOWS |
| FOR ENHANCED FASTENING S-4 FOR THE ROOF ZONE 3 REQUIRES |
| -107. |
| THE RAS 117 CALCULATIONS CAN BE COMPLETED BY EITHER A |
| ARCHITECT, ENGINEER OR REGISTEERED ROOF CONSULTANT. |
| |
| ARCHITECT RESPONSE: ROOFING SHOP DRAWING/ PRODUCT |
| SUBMITTAL SHALL INCLUDE FASTENER CALCULATIONS. |
| FASTENER CALCULATIONS ARE TO BE SUBMITTED AS PART OF |
| THE ROOFING PERMIT UNDER SEPERATE REVIEW. |
| |
| 2) FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF |
| ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN |
| "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE |
| REQUIRED BEFORE A CERTIFICATE OF OCCUPANCY WILL BE |
| ISSUED. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |