Plan Review Notes
Plan Review Notes For Permit 08120369
Permit Number 08120369
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2009-03-06 15:03:35*****UNSAT*****
  
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE STAMPED WHEN THE
 FOLLOWING TWO COMMENTS (OF THE PREVIOUS SEVEN) AS WELL
 AS THE OTHER PLAN EXAMINER'S COMMENTS HAVE BEEN
 ADDRESSED:
  
 3. DISPLAY/SHOW THE LOCATION OF THE FIRE HYDRANTS
 WITHIN 500 FEET OF THE SITE. COULD NOT LOCATE THIS
 HYDRANT AS PER YOUR RESPONSE LETTER
  
 5. IN ADDITION TO ELECTRONIC SWITCHES ON THE DOUBLE
 CHECK DETECTOR ASSEMBLY AS SHOWN ON PAGE C15, THE
 BACKFLOW DEVICE SHALL BE EQUIPPED WITH A CHAIN AND
 LOCK. COULD NOT LOCATE THIS COMMENT AS PER YOUR
 RESPONSE LETTER
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722