 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 THIS COMMENT WAS FROM THE PREVIOUS REVIEW
  
 17} PER 13-415.2.ABC.1.1. PAGE #2 OF THE ENERGY GAUGE
 INPUT DATA REPORT, DOES NOT INDICATE THE CORRECT NUMBER
 OF FIXTURES AS SHOWN ON THE PLAN, THE WATTAGES PER
 LUMINAIRE ARE INCORRECT, AND THE CONTROL TYPE MUST BE
 PER 13-415.1ABC.1.2. NO LIGHTING POWER DENSITIES PER
 13-415, INTERIOR OR EXTERIOR WERE GIVEN. COMPLY WITH
 CHAPTER 13 FBC.***THE EXTERIOR AND INTERIOR WATTAGES
 AND COUNTS DO NOT CORRELATE WITH THE LIGHTING FIXTURE
 SCHEDULE ON SHEET VC E-11.0.
  
 NEW COMMENT, SHEET VC E-5.0
  
 1} THE NOTE REGARDING THE FIXTURES TO BE DETERMINED AT
 A LATER DATE IS NOT ACCEPTABLE. A SYSTEM MUST BE SHOWN
 THAT MEETS THE REQUIREMENTS OF THE CODE. IT MAY BE
 REVISED AT A LATTER DATE. ALSO SEE 13-415.2.ABC.1.2 -3.
 THE WATTAGE OF LINE-VOLTAGE LIGHTING TRACK AND PLUG-IN
 BUSWAY THAT ALLOW THE ADDITION AND/OR RELOCATION OF
 LUMINAIRES WITHOUT ALTERING THE WIRING OF THE SYSTEM
 SHALL BE THE SPECIFIED WATTAGE OF THE LUMINARIES
 INCLUDED IN THE SYSTEM WITH A MINIMUM OF 30 WATTS PER
 LINEAR FOOT.
  
 2} SHEET VC E-10.0 AND AC-1 LOCATE THE AHU'S IN
 DIFFERENT SPACES IN THE ELECTRICAL ROOM. CORRELATE THE
 SHEETS AND SEE 110.26(F)(1)(B) 2005 NEC FOR FOREIGN
 SYSTEMS IN DEDICATED SPACE.
  