2008-12-26 11:28:23 | ZONING REVIEW: FAILED |
| |
| 1) MATERIAL AND COLOR SELECTIONS TO BE CONFIRMED BY |
| J.GOLDBERG. PLANS INDICATED EXPOSED CMU WHICH WAS |
| DISCUSSED TO BE STUCCO-COVERED. |
| 2) CONFIRM LOCATIONS OF ALL BACKFLOW PREVENTERS, FIRE |
| CONNECTIONS SO THEY MAY BE LOCATED AWAY FROM |
| CIRCULATION OR PRIMARY BUILDING ELEVATIONS (SOUTH |
| ELEV). |
| 3) ON LP-1, CONFIRM ALL PLANTS LISTED ARE TO BE USED. |
| COULD NOT FIND SOT ON PLAN. IS THIS SUPPOSED TO BE SPT? |
| 4) ON IR-1, CONFIRM IRRIGATION LINES WILL BE INSTALLED. |
| IT IS NOT CLEAR FROM THIS DRAWING OR THE NOTES WHAT |
| WILL HAPPEN WITH PRELIM PHASES (LINES SHOULD BE IN |
| PLACE FOR PLANTERS). |
| 5) A 1/A-1.0 - ACCESS RAMP SECTION. CABLE RAILING IS |
| INDICATED ON SOUTHERN SIDE OF RAMP UP. DO WE NEED THIS |
| AT ALL? PLANTER PROVIDES BARRIER AND HANDRAIL IS |
| PROVIDED ON NORTH SIDE, SO CABLING SHOULD NOT BE |
| NECESSARY. CAN WE ELIMINATE THE CABLING AND HANDRAIL? |
| IF NOT, JUST INSTALL HANDRAIL. |
| 6) A-1.1 - DURING TEMPORARY ACCESS PHASE, IT DOES NOT |
| APPEAR THAT THERE WILL BE ENOUGH WHEELCHAIR MANEUVERING |
| CLEARANCE WHEN BATHROOM DOORS ARE OPEN. ACCESS AREA IS |
| OVER 5' WIDE, DOORS WILL BLOCK WHEN OPEN. PLEASE |
| CONFIRM THIS MEETS ADA REQUIREMENTS. |
| 7) ON A-1.1, SCHEMATIC DRAWINGS SHOWED BATHROOM |
| ENTRANCES RECESSED SO THAT THEY WOULD NOT BE DIRECTLY |
| VIEWED FROM EXTERIOR. PLANS SHOW DOORS OPENING DIRECTLY |
| TO THE OUTSIDE. CAN THE PLANS BE REVISED TO SHOW |
| ORIGINAL SCHEMATIC DESIGN, WITH SOME MODIFICATION? THIS |
| CREATES A BETTER SOUTH BUILDING ELEVATION. |
| 8) ON CABLE RAIL DETAILS, RAIL SYSTEM SHOULD NEVER |
| TERMINATE INTO BUILDING ELEVATION. IT SHOULD ALWAYS |
| TERMINATE INTO VERTICAL STEEL SUPPORT WITH TIE-OFF. |
| DETAILS SEEM TO SHOW THIS, BUT JUST CONFIRM. |
| 9) A-5.0 - ALUM DOWNSPOUT INDICATED WITH HORIZONTAL |
| STRUTS CONNECTING TO MAIN BUILDING. WHAT IS THE DETAIL |
| FOR THE CONNECTION TO THE BUILDING? CONFIRM STRUTS |
| ALIGN WITH STRUCTURAL GRID. |
| 10) NOTE FOR ALL PLANTERS THAT ALL CONSTRUCTION DEBRIS |
| SHALL BE REMOVED PRIOR TO FILLING WITH SOIL. |
| 11) S-1 -CONNECTION FROM DOWNSPOUT TO BUILDING NOT |
| SHOW. (SEE NOTE #7). |
| 12) S-1A - FOUNDATION NOTES ARE INCOMPLETE: ELEVATION |
| 100'-0" IS X.XX NGVD. WHAT IS X.XX? |
| 13) TREE ALTERATION PERMIT WILL BE REQUIRED FOR THE |
| ENTIRE CITY COMMONS SITE. PLANNING STAFF WILL |
| COORDINATE WITH THE LANDSCAPE ARCHITECT. CONTACT ROBERT |
| KUSSNER, LANDSCAPE PLANNER, AT 822-1435. |
| 14) ON SP-1, AT THE NORTHWEST CORNER OF THE VISITOR |
| CENTER, WHAT IS THE TRANSITION FROM THE LANDSCAPED AREA |
| TO THE EXISTING PAVERS? THERE DOES NOT APPEAR TO BE ANY |
| HEADER CURB OR OTHER EDGE. ALSO, THE SHAPE OF THIS |
| LANDSCAPE AREA CHANGES BETWEEN THE DIFFERENT PLANS. |
| CONFIRM THE ACTUAL LIMITS. |
| 15) OTHER LANDCAPE COMMENTS WILL BE PROVIDED THROUGH |
| SEPARATE LANDSCAPE REVIEWER. |
| |
| MATT FLIS - 822-1445 |